Wiring Idp Slc Detectors - Honeywell SILENT KNIGHT RPS-2000 Installation And Operation Manual

Analog/addressable fire system
Table of Contents

Advertisement

7.4

Wiring IDP SLC Detectors

This section describes how to install IDP heat and smoke detectors. All detectors ship with
installation instructions. Refer to each detectors installation instructions for more detailed
information.
This information applies to the following IDP models:
IDP-Photo Photoelectric Smoke Detector
IDP-Photo-T Photoelectric Smoke Detector with Thermal
IDP-Acclimate Photoelectric Smoke Detector with Thermal
IDP-Heat Fixed Temperature Detector
IDP-Heat-T High Temperature Thermal Detector
IDP-Heat-ROR Rate-of-Rise Thermal Detector
IDP-Ion Ionization Smoke Detector
To wire IDP detectors:
1. Wire device bases as shown in Figure 7-4
2. Set the address for each device as described in Section 7.5
Class B wiring
Figure 7-4 Heat and Smoke Detector Connection to the Panel.
151430
Caution: Do not loop wire under Terminal 1 or 2.
Break wire run to provide supervision of connections.
firealarmresources.com
IDP SLC Device Install
Class A wiring
7-5