7.4
Wiring IDP SLC Detectors
This section describes how to install IDP heat and smoke detectors. All detectors ship with
installation instructions. Refer to each detectors installation instructions for more detailed
information.
This information applies to the following IDP models:
•
IDP-Photo Photoelectric Smoke Detector
•
IDP-Photo-T Photoelectric Smoke Detector with Thermal
•
IDP-Acclimate Photoelectric Smoke Detector with Thermal
•
IDP-Heat Fixed Temperature Detector
•
IDP-Heat-T High Temperature Thermal Detector
•
IDP-Heat-ROR Rate-of-Rise Thermal Detector
•
IDP-Ion Ionization Smoke Detector
To wire IDP detectors:
1. Wire device bases as shown in Figure 7-4
2. Set the address for each device as described in Section 7.5
Class B wiring
Figure 7-4 Heat and Smoke Detector Connection to the Panel.
151430
Caution: Do not loop wire under Terminal 1 or 2.
Break wire run to provide supervision of connections.
firealarmresources.com
IDP SLC Device Install
Class A wiring
7-5