Honeywell SILENT KNIGHT RPS-2000 Installation And Operation Manual page 165

Analog/addressable fire system
Table of Contents

Advertisement

with a water flow switch. The delay is system-wide. All water flow switches on the system
will use the same delay period.
To access the screen for programming water flow delay, follow these steps:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select
for Panel Programming.
7
Display reads:
3. Select
for System Options.
5
4. Select
for Miscellaneous Options 1.
4
A screen similar to the one shown in Figure 9-11 will display.
Figure 9-11 Water Flow Delay Programming Screen
5. Enter the number of seconds (0 to 90) to delay a water flow switch alarm, then press
.
151430
Initializing
Please wait . . .
firealarmresources.com
Delay in seconds before waterflow
alarm occurs (00-90)
Programming
9-29

Advertisement

Table of Contents
loading