Honeywell SILENT KNIGHT RPS-2000 Installation And Operation Manual page 113

Analog/addressable fire system
Table of Contents

Advertisement

IDP SLC Device Install
Figure 7-1 and Figure 7-2 show how wire length is determined for out-and-back tap and T-tap
style wiring.
Figure 7-1 Calculating wire run length for a simple out and back tap
When using T-taps, the total length of all taps and the main bus must not exceed 40,000 feet.
This requirement must be met in addition to the maximum distance requirements for the
various wire gauges.
Figure 7-2 Calculating Wire Run Length for a T-tap
151430
7-3