Remote Station Applications; Keltron Model 3158 Installation - Honeywell SILENT KNIGHT RPS-2000 Installation And Operation Manual

Analog/addressable fire system
Table of Contents

Advertisement

IFP-2000 Installation Manual
1. Wire Relay 1 and/or Relay 2 as needed for your application. See Figure 4-41 for the loca-
tion of the relay terminals.
2. Configure the relay through programming (see Section 9.5).

4.15 Remote Station Applications

4.15.1 Keltron Model 3158 Installation

The control panel is compatible with Keltron Model 3158, used for direct connection to a
Keltron receiver. The 3158 reports alarms, supervisories, and troubles.
The steps for connecting the 3158 to the control panel. Refer to the 3158 installation
instructions for complete information.
1. Wire the 3158 to the control panel as shown in the connection list and Figure 4-42.
2. Wire the 3158 within 20 feet of the control panel. Wiring must be enclosed in conduit.
3. Program control panel Relay 1 for alarm.
4. Program Flexput circuit 5 for alarm.
5. Program Flexput circuit 6 for supervisory non latching.
Table 4-5: Keltron 3158 to Control Panel Connections
Terminal #
3158 Term. 1
To Keltron receiving equipment
3158 Term. 2
To Keltron receiving equipment
3158 Term. 3
Earth ground
3158 Term. 4
Not used; no connection.
3158 Term. 5
Control panel SBUS OUT +
3158 Term. 6
Control panel SBUS OUT –
3158 Term. 7
Control panel I/O5 O
4-42
Connects To
3158 Term. 8
3158 Term. 9
3158 Term. 10
Control panel I/O5 X
Control panel Relay 1 COM Control panel Trouble COM
Control panel Relay 1 NO
firealarmresources.com
Terminal #
Connects To
Control panel Relay 1 COM
Control panel I/O6 O
Control panel I/O6 X
Control panel Relay 1 NO
Control panel Trouble NC
151430