2. Check the voltage at the connector. Make sure it is within the
required voltage range.
3. If the voltage is within the specified range, connect the power
connector to the unit.
4. Close and secure the housing door; verify the fan starts up and
air flows out of the exhaust port. The unit takes 1-3 minutes to
initialise and stabilise in normal mode.
Configuring Other Options
To change any of the default options, it will be necessary to
connect the detector to a PC/laptop with the PipeIQLT software
installed; see USB connection section later in this guide for
more information on this (and the FAAST LT Advanced Setup and
Control Guide).

EXTERNAL RESET

The default setting for the configurable external input is Device
Reset (terminal block T8). A short circuit connection between these
terminals will cause the FAAST LT unit to perform a reset.

FRONT PANEL

The front panel will be different depending on which of the 3 NFXI-
ASD models is being installed, and each is shown below.
The following information is displayed:
Detector Status: Normal, Alarm, Fault or Isolate
Alarm Level; Alarm, Pre-Alarm (only available with panels
using Advanced Protocol)
Particulate Levels; 1-9 (only available with panels using
Advanced Protocol)
Flow Level
Test, Reset and Disable Buttons
Figure 11: Front Panel Display
10
9
8
7
6
5
4
3
2
SMOKE
LEVEL
1
MODULE
FAULT
11a: NFXI-ASD11 1 Channel Detector (1 Sensor)
N200-102-00
Notifier Ltd., Charles Avenue, Burgess Hill, West Sussex, RH15 9UF, UK
ALARM
PREALARM
POWER
FAULT
SMOKE
LEVEL
MODULE
FAULT
11b: NFXI-ASD12 1 Channel Detector (2 Sensors)
SMOKE
LEVEL 1
MODULE 1
FAULT
11c: NFXI-ASD22 2 Channel Detector
6
ALARM
PREALARM
10
9
8
7
6
5
4
3
2
1
POWER
FAULT
ALARM
PREALARM
10
10
9
9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
SMOKE
1
1
LEVEL 2
MODULE 2
POWER
FAULT
I56-3947-200

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents