2. Use the 5' ribbon cable to connect the IFP-2000 to the repeater board. Run an insulated
wire from the screw terminal labeled TB2 on the repeater to an earth screw terminal on the
control panel.
Figure 5-6 Panel to Networked repeater connection
3. Place jumper J1 (also labeled TERM) for ALL repeater installations.
4. Place Jumpers J2 and J3 when there is a twisted pair cable connected to positions 1 and 2
of terminal black TB1. Each repeater has the ability to monitor for earth ground faults on
the twisted pairs connected to terminals 1 and 2 of its terminal block TB1. Earth fault
detection for any wiring at terminals 3 and 4 of TB1 is done at the next/previous repeater
due to these wiring connections being connected to terminals 1 and 2 of TB1 at the next/
previous repeater. When no twisted pair wiring is made to terminals 1 and 2 of TB1
jumpers J2 and J3 must be left OPEN at the repeater. This would be the case when using
fiber optic cable or when terminals 3 and 4 of TB1 are only being used.
5. On fiber optic repeaters, jumpers J4 through J9 are normally left OPEN. See IFP-RPT
installation instruction (p/n 9001-0061) for determining when to use J4 through J9. Fiber
optic ports that are not used must have their dust caps placed on the port.
6. Based on the type of network repeater board chosen, run the twisted pair wiring /fiber
optic cable to the next network repeater using a BUS or style 7 (class A) wiring method. A