Honeywell SILENT KNIGHT RPS-2000 Installation And Operation Manual page 153

Analog/addressable fire system
Table of Contents

Advertisement

Type
Function
Selection
OUTPUT PT
Select Group
AUX CONST
NOTIF
AUX RESET
AUX DOOR
OUTPUT PT
Select Group
AUX RESET
RELAY
AUX DOOR
151430
Latching Option
Output Point, a general use notification type. Use for driving standard
notification appliances.
Use constant power for applications that require a constant auxiliary power
source. Power is always present at Constant circuits.
Use for auxiliary power, resettable applications. See Section 4.13.5.3 for a
description of how this option operates.
Use for auxiliary power, door holder applications. For example, if you were
using an auxiliary power supply for door holders, you would use this option.
See Section 4.13.5.1 for a description of how this option operates.
Output Point, a general use relay type. Use for applications requiring a relay,
such as fan shutdown, elevator recall, and so on.
Use for auxiliary power, resettable applications. See Section 4.13.5.3 for a
description of how this option operates.
Use for auxiliary power, door holder applications. For example, if you were
using an auxiliary power supply for door holders, you would use this option.
See Section 4.13.5.1 for a description of how this option operates.