6.2.6.1 Dialer Assignments

Each panel on the IFP-2000 network specifies which network dialer is used for reporting. The
network dialer capability of the IFP-2000 system allows all panels to use the same dialer
providing an economical solution for reducing the number of phone lines required for
reporting purposes. A dialer is specified by panel number. The network dialers will be used to
report events according to the dialer report table.

6.2.6.2 Dialer Miscellaneous

When using the SIA reporting format, the dialer sends modifier information according to the
SIA Modifier option. The selections for this option are enable PI SIA Modifier, Yes or No.
The default selection is Yes which will report the same as IFP-1000 version 9 panels. If set to
"No", the panel ID will be included as part of the SIA event string.

6.2.6.3 Receiver Configuration

The IFP-2000 network can report events to as many as four receivers. Each receiver is
assigned a phone number and reporting format. Phone numbers can be up to forty digits long.
Format choices are SIA, Contact ID, or Unused.

6.2.6.4 Dialer Report Table

The Dialer Report Table specifies event reporting for each panel on the network. Each row in
the table specifies a panel, event types to report, primary and backup reporting channel, and
report by point or zone. Associated with the receivers are account number and daily test
option. The table can have up to 99 rows.