3. Configure the network terminators. The panels at both ends of the network bus must have
DIP switches 8, 9, and 10 set to the "ON" position. All panels that are not at the BUS ends
must have the terminators set to the OFF position. See Figure 5-2
4. T-Tapping is not allowed, wire must be run in a BUS configuration.
Figure 5-2 DIP Switch terminations settings for Direct Connect Wiring option
151430