Adding A Module; Deleting A Module - Honeywell SILENT KNIGHT RPS-2000 Installation And Operation Manual

Analog/addressable fire system
Table of Contents

Advertisement

IFP-2000 Installation Manual
9.2.2

Adding a Module

If you need to add a new hardware module to the system, follow these steps.
You must be in the Main Menu to perform this task. If necessary, enter the Installer Code.
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select
for Panel Programming.
7
Display reads:
3. Press
to enter module menu.
1
4. Press
to add a module.
2
5. From the next screen, select the number that corresponds to the type of module you are
adding from the <New Module Type> screen.
The screen will display "Adding module [#]..." for a few moments. You will be returned to
the <New Module Type> screen where you can select a name for the module if desired.
You must save changes when you exit the Panel Programming or the new module will not be
added.
Note: If you Add a Module that has not been physically connected, the panel will go into trouble after it
reinitializes (when you exit the Panel Programming). When the new module is attached, the trouble will
correct itself automatically the next time you power up the system.
9.2.3

Deleting a Module

If you ever need to delete a module, follow these steps.
You must be in the Main Menu to perform this task. If necessary, enter the Installer Code.
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select
for Panel Programming.
7
Display reads:
1
3. Press
to enter module menu.
4. Press
to delete a module.
3
5. A warning screen will display. If you want to proceed with deleting the module, select
Yes. To cancel, select No.
9-4
Initializing
Please wait . . .
Initializing
Please wait . . .