4.15.4.2 Using the 7644 Module

When the 7644 is used for polarity reversal, it allows alarm and trouble events to be reported
to a remote site. Alarms will override trouble conditions and it will not be possible to reset the
remote indicator until the condition is cleared and the control panel is reset.
To install the 7644 for polarity reversal:
1. Wire the 7644 to the control panel as shown in Figure 4-46. Do not install an EOL resistor
on the terminals of the flexput circuit used.
Note: Use only Flexput circuits on the control panel for reverse polarity.
2. Program the Flexput circuit as a notification circuit. See Section 9.5.2.
3. Map the group to activate non silenceable constant on in response to a system general
alarm, and to disconnect in response to a system trouble.
4. Intended for connection to a polarity reversal circuit of a remote station receiving unit
having compatible rating.
Figure 4-46 Polarity Reversal Connection Using the 7644
151430
firealarmresources.com
Control Panel Installation
4-47