Siemens SITRANS L Operating Instructions Manual page 61

Radar transmitters with foundation fieldbus
Hide thumbs Also See for SITRANS L:
Table of Contents

Advertisement

Parameter type
Quick Start
Wizard parame-
ters
Independent
parameters
Return to Measurement: press Mode
SITRANS LR250 with FOUNDATION FIELDBUS
Operating Instructions, 09/2021, A5E32221411-AH
Sensor reference point
0.5 m
High calibration point
3.5. m
Low calibration point
Parameter Name
Introduction
Language
Material
Response Rate
Units
Low Calibration Point
High Calibration Point
Wizard Complete
Vessel Shape (2.4.1.1.)
PV (volume/level) Units
(2.3.3.)
Level Unit (2.3.2.)
Maximum Volume (2.4.1.2.)
Dimension A (2.4.1.3.)
Dimension L (2.4.1.4.)
Loss of Echo (LOE) Timer
(2.3.6.)
A = 0.8 m
L = 6 m
100% = 8000 L
Volume reading
Options/
Values
NEXT
NEXT
LIQUID
MED
M
3.5
0.5
FINISH
PARABOLIC
ENDS
L
M
8000
0.8
6
120
to start normal operation.
Commissioning
6.3 Application examples
Function
Continue with Wizard.
Continue with current language.
Medium =1 m/minute
meters
3.5 m (11.48 ft)
0.5 m (1.64 ft)
Transfers Quick Start settings to
device.
Defines vessel shape.
liters
meters
8000 liters
0.8 m (2.62 ft)
6 m (19.68 ft)
120 seconds
61