Parameter reference
Unit (2.6.4.3.)
Engineering unit to be displayed with the output value.
Values
Decimal Point (2.6.4.4.)
Read only. The number of digits to display after the decimal point (set to 0 decimal places).
Output Scaling (2.6.5.)
Scales the Process Variable. The function block parameter OUT SCALE contains the values of
the lower limit and upper limit effective range in AIFB 1 units.
Lower Value (2.6.5.1.)
Defines the operational lower range value of the output value in AIFB 1 units.
Values
Upper Value (2.6.5.2.)
Defines the operational upper range value of the output value in AIFB1 units.
Values
142
m, cm, mm, ft, in, cu m, L, HL, cu in, cu ft, cu yd, gal, imp gal,
bushels, Bbl, Bbl liquid, percent, PA, Follow out unit
*
%
Range: -999999 to 999999
Default: 0%
Range: -999999 to 999999
Default: 100%
Provides Output values
(Out) to AIFB 1 or AIFB 2
SITRANS LR250 with FOUNDATION FIELDBUS