Diagnosing and troubleshooting
10.3 Operation troubleshooting
Code/
Meaning
Icon
S: 114
Addr Bus
S: 115
Spur SW
S: 116
Spur HW
S: 117
SV High
S: 118
SV Low
10.3
Operation troubleshooting
Operating symptoms, probable causes, and resolutions.
Symptom
Display shows
Display shows
Display shows
Display shows
176
Cause
level or target is out of range
material build-up on antenna
location or aiming:
poor installation
flange not level
Auto False Echo Suppression
may be incorrectly applied
antenna malfunction:
temperature too high
physical damage
excessive foam
multiple echoes
Corrective Action
Hardware problem. If fault persists contact your local Sie-
mens representative.
Hardware problem. If fault persists contact your local Sie-
mens representative.
Hardware problem. If fault persists contact your local Sie-
mens representative.
Verify TB not in simulation mode. If fault persists contact
your local Siemens representative.
Verify TB not in simulation mode. If fault persists contact
your local Siemens representative.
Action
check specifications
check Low Calibration Pt. (2.3.7.1.)
increase Confidence (2.5.9.1.)
clean the antenna
re-locate SITRANS LR250
check to ensure nozzle is vertical
ensure end of antenna protrudes from end of nozzle
review Auto False Echo Suppression (Page 238)
ensure Auto False Echo Suppression Range is set correctly
check temperature in Maximum Value (3.3.2.)
use foam deflector or stillpipe
relocate
use a defoamer
set Algorithm (2.5.7.1.) to tF (trueFirst echo)
SITRANS LR250 with FOUNDATION FIELDBUS