Parameter reference
Linearization Table must be selected in order for level/volume values [see XY
a)
index (2.4.1.5.)] to be transferred.
Maximum Volume (2.4.1.2.)
The maximum volume of the vessel. Units are defined in PV Units (volume/ level) (2.3.3.).
Enter the vessel volume corresponding to High Calibration Point. The volume calculation is
based on the maximum volume and scaled according to the vessel shape selected. If no
vessel shape is entered, the default is 100, and the reading will be a percentage value.
Values
Related Parameters
128
Vessel Shape
Range: 0.0000 to 999999
Default: 100.0
Low Calibration Pt. (2.3.7.1.)
High Calibration Pt. (2.3.7.2.)
Vessel Shape (2.4.1.1.)
LCD DISPLAY/ Description
HALF SPHERE BOT/
Half-sphere bottom
FLAT SLOPED BOT/
Flat sloped bottom
PARABOLIC ENDS/
Parabolic end horizontal
cylinder
LINEAR TABLE
/ Lineariza-
a)
tion table (level/volume
breakpoints)
SITRANS LR250 with FOUNDATION FIELDBUS
Operating Instructions, 09/2021, A5E32221411-AH
Also required
Maximum volume,
dimension A
Maximum volume,
dimension A
Maximum volume,
dimension A, dimension
L
Maximum volume, level
breakpoints, volume
breakpoints