Siemens SITRANS L Operating Instructions Manual page 125

Radar transmitters with foundation fieldbus
Hide thumbs Also See for SITRANS L:
Table of Contents

Advertisement

Sensor Offset (2.3.7.3.)
A constant offset that can be added to or subtracted from the sensor value to compensate for
a shifted sensor reference point. (For example, when adding a thicker gasket or reducing the
standoff/nozzle height.) The units are defined in Unit (2.3.1.).
Values
Related Parameters
See How the LTB works: in manual Foundation Fieldbus for Level Instruments
(7ML19985MP01) for more details on sensor offset.
Low Level Point (2.3.7.4.)
The level when the material is at Low Calibration Point. The unit is defined in Level Unit
(2.3.2.).
Values
High Level Point (2.3.7.5.)
The level when the material is at High Calibration Point. The unit is defined in Level Unit
(2.3.2.).
Values
Level Offset (2.3.7.6.)
A constant offset that can be added to Level. The unit is defined in Level Unit (2.3.2.).
Values
Rate (2.3.8.)
Response Rate (2.3.8.1.)
Sets the reaction speed of the device to measurement changes.
Note
Changing Response Rate resets Fill Rate per Minute (2.3.8.2), Empty rate per Minute
(2.3.8.3), and Shots (2.5.6.).
SITRANS LR250 with FOUNDATION FIELDBUS
Operating Instructions, 09/2021, A5E32221411-AH
Range: -99.999 to 99.999 Default: 0.000 m
Unit (2.3.1.)
Range: -999999 to 999999
Default: 0%
Range: -999999 to +999999
Default: 100%
Range: -999999 to +999999
Default: 0%
Parameter reference
125