Siemens SITRANS L Operating Instructions Manual page 239

Radar transmitters with foundation fieldbus
Hide thumbs Also See for SITRANS L:
Table of Contents

Advertisement

Auto False Echo Suppression Range must be set to a distance shorter than the distance to the
material level when the environment was learned, to avoid the material echo being screened
out.
Example before Auto False Echo Suppression
Example after Auto False Echo Suppression
SITRANS LR250 with FOUNDATION FIELDBUS
Operating Instructions, 09/2021, A5E32221411-AH
Default TVT
False echo
Material echo
Sensor reference point
Learned TVT
False echo
Auto False Echo Suppression Range
Appendix A: Technical reference
High calibration point = 0
Obstruction at 1.3. m
Material level at 3.2 m
Default TVT
Material echo
Echo marker
A.2 Echo processing
Auto False Echo
Suppression
Range set to 2 m