Siemens SITRANS L Operating Instructions Manual page 145

Radar transmitters with foundation fieldbus
Hide thumbs Also See for SITRANS L:
Table of Contents

Advertisement

Output, no level offset (SV2 - Secondary Value 2) (2.8.3.)
The value for distance.
Diagnostics (3.)
Echo Profile (3.1.)
Allows you to request the current echo profile via the handheld programmer, or via AMS
Device Manager. For more detail see Echo Processing (Page 233).
To request a profile via AMS Device Manager:
See Echo Profile (Page 84).
To request a profile via the handheld programmer:
1. Navigate to Level Meter > Diagnostics (3.) > Echo Profile (3.1.).
2. Press RIGHT arrow to request a profile. [See Requesting an Echo Profile (Page 57) for more
details.]
Fault Reset (3.2.)
Clears faults (see chart below).
Clearing a fault in one parameter of a 'maintenance pair', automatically clears a fault in the
second parameter of the pair. For example, entering S3 or S4 will clear a fault on Device
Lifetime Reminder 1 (Maintenance Required), and on Device Lifetime Reminder 2
(Maintenance Demanded). This applies when clearing faults via the handheld programmer,
or the 375 Field Communicator.
Fault code
S3
S4
S6
S7
S8
S9
S12
S17
S18
To clear a fault using the handheld programmer:
• Enter the fault code number then press RIGHT arrow
SITRANS LR250 with FOUNDATION FIELDBUS
Operating Instructions, 09/2021, A5E32221411-AH
Description
Device Lifetime Reminder 1 (Maintenance Required)
Device Lifetime Reminder 2 (Maintenance Demanded)
Sensor Lifetime Reminder 1 (Maintenance Required)
Sensor Lifetime Reminder 2 (Maintenance Demanded)
Device Service Reminder 1 (Maintenance Required)
Device Service Reminder 2 (Maintenance Demanded)
Internal Temperature High
Calibration Schedule Reminder 1 (Maintenance Required)
Calibration Schedule Reminder 2 (Maintenance Demanded)
Parameter reference
.
145

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans lr250

Table of Contents