Siemens SITRANS L Operating Instructions Manual page 147

Radar transmitters with foundation fieldbus
Hide thumbs Also See for SITRANS L:
Table of Contents

Advertisement

Reset Type
Factory Defaults
Standard Defaults
Informational
Functional
Warm Start
FF Object Dictionary
The only difference between Factory Defaults and Functional reset is that Factory Defaults resets
a)
maintenance parameters, such as device and sensor wear, calibration and maintenance timers.
Functional reset does not reset these parameters.
See Data transmission in manual Foundation Fieldbus for Level Instruments (7ML19985MP01) for
b)
further details.
To access via AMS Device Manager see Master Reset under Operation (RESOURCE) (Page 93).
To perform a reset via the handheld programmer:
1. Press RIGHT arrow
press RIGHT
2. Press LEFT arrow
After performing a master reset, the device will stop measuring, the Resource and Level
Transducer Blocks will go to Out of Service, and the LUI will show the Quick Start Wizard
until the device is configured.
Remaining Device Lifetime (4.2.)
Note
• Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly
stated.
• Four sets of parameters allow you to monitor the Device/Sensor Lifetimes and set up
Maintenance/Service schedules, based on operating hours instead of a calendar-based
schedule. See also Remaining Sensor Lifetime (4.3.), Service Schedule (4.4.), and
Calibration Schedule (4.5.).
• Performing a reset to Factory Defaults will reset all the Maintenance Schedule
parameters to their factory defaults.
• The device operates in years. To view Remaining Device Lifetime parameters in hours (via
AMS Device Manager only) see Remaining Device Lifetime under Maintenance &
Diagnostics (RESOURCE) (Page 95).
The device tracks itself based on operating hours and monitors its predicted lifetime. You can
modify the expected device lifetime, set up schedules for maintenance alerts, and
acknowledge them.
SITRANS LR250 with FOUNDATION FIELDBUS
Operating Instructions, 09/2021, A5E32221411-AH
Result
Default. Resets all user parameters to the manufacturer's default settings.
a)
Following this type of reset, complete reprogramming is required.
Resets all parameters to standard default settings.
Resets parameters such as Block Descriptor, Strategy, Device Install Date,
Device Message.
Resets parameters that control device behavior and functionality (such as
a)
Low Calibration Point).
Has the same effect as recycling power to the device.
Resets the FF standard block profile parameters (such as block tags) to
their specified defaults. This option also clears any function block parame-
ters and device schedule
to open Edit Mode then scroll down to the desired reset type and
arrow to select it.
to exit.
set by the user.
b)
Parameter reference
147