Maintenance Status (4.2.7.)
Indicates which level of maintenance reminder is active.
To display the level of maintenance reminder that is active in AMS Device Manager see
Extended Diagnostics under Device Diagnostics [Resource Block - RESOURCE (Page 102)].
Acknowledge Status (4.2.8.)
Indicates which level of maintenance reminder has been acknowledged.
Acknowledge (4.2.9.)
Acknowledges the current maintenance reminder.
To acknowledge a reminder via the handheld programmer:
1. Press RIGHT arrow
2. Press RIGHT arrow
Remaining Sensor Lifetime (4.3.)
Note
• Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly
stated.
• Four sets of parameters allow you to monitor the Device/Sensor Lifetimes and set up
Maintenance/Service schedules, based on operating hours instead of a calendar-based
schedule. See also Remaining Device Lifetime (4.2.), Service Schedule (4.4.), and
Calibration Schedule (4.5.).
• Performing a reset to Factory Defaults will reset all the Maintenance Schedule parameters
to their factory defaults.
• The device operates in years. To view Remaining Sensor Lifetime parameters in hours (via
AMS Device Manager only) see Remaining Sensor Lifetime in Maintenance & Diagnostics
(LTB) (Page 85).
The device monitors the predicted lifetime of the sensor (the components exposed to the
vessel environment). You can modify the expected sensor lifetime, set up schedules for
maintenance reminders, and acknowledge them.
To access these parameters via AMS Device Manager see Remaining Sensor Lifetime in
Maintenance & Diagnostics (LTB) (Page 85).
Lifetime (expected) (4.3.1.)
Allows you to override the factory default.
Values
SITRANS LR250 with FOUNDATION FIELDBUS
Operating Instructions, 09/2021, A5E32221411-AH
twice to open parameter view and activate Edit Mode.
to acknowledge the reminder.
Units: years
Range: 0 to 20 years
Default: 10.00 years
Parameter reference
149