Starting The Heating System - Viessmann VITOLIGNO 300-C Installation And Service Instructions Manual

Pellet boiler 60 to 70 kw
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Setting the heating curves
Reduced room temperature
110
A
C
B -20°C
D
Fig. 62
Changing the reduced room temperature
from 3 to 14 °C
Flow temperature in °C
A
Outside temperature in °C
B
C
Set room temperature in °C
Heating circuit pump off
D
Heating circuit pump on
E
Changing the slope and level
The heating curve can be adjusted separately for each
heating circuit.
110
3.5
A
+20
Outside temperature in °C
Fig. 63
Changing the slope.
A
Changing the level (vertical parallel offset of the
B
heating curve).

Starting the heating system

Switch ON the heating system by pressing the
"START/STOP" button on the boiler.
78
(cont.)
14°C
3°C
E
1.4
B
0.2
-20
Press the following keys:
1.
.
å
2.
/
For selecting the heating circuit.
|
~
3.
To confirm.
d
4.
/
For "Reduced room temperature".
|
~
5.
To confirm.
d
6.
/
For the required value.
|
~
7.
To confirm.
d
Press the following keys:
1.
.
å
2.
/
For selecting the heating circuit.
|
~
3.
To confirm.
d
4.
/
For "Heating curve".
|
~
5.
To confirm.
d
6.
/
For "Slope" or "Level".
|
~
7.
d
To confirm.
8.
/
For the required value.
|
~
9.
To confirm.
d
10. Press
to return to default display.
ä

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vl3c

Table of Contents