Viessmann VITOLIGNO 300-C Installation And Service Instructions Manual page 135

Pellet boiler 60 to 70 kw
Table of Contents

Advertisement

High limit safety cut-out
B
A
Fig. 81
Sensors
Sensor type Pt1000:
Flow temperature sensor
Buffer temperature sensor
Return temperature sensor
Flue gas temperature sensor
Outside temperature sensor
Connection
See chapter "Connection and wiring diagram" from
page 184.
Checking the sensors
Flue gas temperature sensor
1.75
1.25
0.75
A
50
0
Temperature in °C
Fig. 82
Data point shown: Resistance of 1.1 k
A
perature of 25 °C
(cont.)
150
200
100
at a tem-
Ω
1. Move cover
A
on the programming unit to the
right.
2. Press green button
B
out.
A quiet "click" will be audible. The high limit safety
cut-out has been reset.
3. Close cover
on the programming unit.
A
4. Acknowledge excess temperature at the program-
ming unit with
d
.
Curve of the sensor from the extension kit for heating
circuit with mixer:
Extension kit installation instructions
250
Maintenance
of the high limit safety cut-
135