Code 1
(cont.)
Coding in the delivered condition
Discharge cycle ON
30:...
Cycle, discharge
(discharge runs for ... seconds)
Discharge cycle OFF
31:...
Pause, discharge
Discharge delay
32:...
Discharge delay
External charging cycle ON
40:...
External charging cycle
(external charging runs
for ... seconds)
External charging cycle OFF
41:...
External charging pause
External charging delay
42:...
External charging delay
Buffer (heating water buffer cylinder)
Coding
Coding in the delivered condition
Buffer cylinder temperature reheating suppression
33:0
Reheating suppression disabled
Maximum buffer cylinder temperature
34:...
Maximum average temperature of
the heating water buffer cylinder
(upper limit of control range)
Minimum buffer cylinder temperature
35:...
Minimum average temperature of
the heating water buffer cylinder
(lower limit of control range)
Possible change
30:2
Setting range in seconds
to
30:120
31:0
Discharge does not pause: Continu-
ous operation
31:1
Setting range in seconds
to
31:100
32:0
Setting range in seconds
to
32:100
40:2
Setting range in seconds
to
40:120
41:0
External charging does not pause:
Continuous operation
41:1
Setting range in seconds
to
41:100
42:0
Setting range in seconds
to
42:100
Possible change
33:1
Set temperature of the heating water
to
buffer cylinder for solar charging.
33:100
Setting range in °C
34:30
Setting range in °C
to
34:100
35:30
Setting range in °C
to
35:100
Codes
105