Viessmann VITOLIGNO 300-C Installation And Service Instructions Manual page 103

Pellet boiler 60 to 70 kw
Table of Contents

Advertisement

Code 1
(cont.)
General
Coding
Coding in the delivered condition
Detached house/apartment building
7F:1
Detached house, same holiday
program setting for all Heating
groups.
Minimum temperature, top buffer sensor
91:0
No minimum temperature
Boiler
Coding
Coding in the delivered condition
Runtime boiler load
01:...
Maximum runtime of the boiler at
full load before the boiler switches
to grate cleaning.
Flue gas residual O2
0C:...
Set value for concentration of re-
sidual oxygen in the flue gas
Boiler water temperature limit
0E:...
Maximum boiler water temperature 0E:70
Min boiler return
12:...
Minimum boiler return temperature 12:...
Flue gas fan start speed
3C:...
Speed of the flue gas fan when the
boiler starts (heat-up)
Flue gas fan minimum speed
3D:...
Minimum speed of flue gas fan
Flue gas fan maximum speed
3E:...
Maximum speed of flue gas fan
Possible change
7F:0
Apartment building, holiday pro-
grams can be adjusted separately.
91:1
If a combined heating water buffer
to
cylinder is installed, a minimum tem-
91:95
perature can be set for the top of the
buffer cylinder (captured by buffer
temperature sensor 1).
Setting range in °C
Possible change
01:....
Setting range in minutes
to
01:....
0C:...
Setting range in 0.1 % increments
to
0C:...
Setting range in °C
to
0E:90
Setting range in °C
to
12:...
3C:...
Setting range in %
to
3C:...
3D:...
Setting range in %
to
3D:...
3E:...
Setting range in %
to
3E:...
Codes
103