Viessmann VITOLIGNO 300-C Installation And Service Instructions Manual page 101

Pellet boiler 60 to 70 kw
Table of Contents

Advertisement

Code 1
(cont.)
Coding in the delivered condition
Buffer type
Buffer type:0
When heat is drawn from the heat-
ing water buffer cylinder, actual
system temperature = temperature
at buffer temperature sensor 1.
Only available if code "Buffer: 3, 4
or 5".
(basic heating water buffer cylin-
der)
Cascade
Cascade:No
No cascade of boilers selected
Cascade charging
Cascade:No
No common charging of boilers se-
lected.
Charging scheme
Charging
Automatic charging with vacuum
scheme:1
module for vacuum supply system
from a pellet silo and for discharge
with manual changeover unit from
a pellet store.
DHW
DHW:No
No DHW heating installed
Possible change
Buffer type:1
When heat is drawn from the heat-
ing water buffer cylinder, actual sys-
tem temperature = temperature at
buffer temperature sensor 2.
(combi cylinder)
Cascade:1
The boiler is boiler number 1 (mas-
ter boiler) in the boiler cascade.
Cascade:2
Boiler number 2 in the boiler cas-
cade.
Cascade:3
Boiler number 3 in the boiler cas-
cade.
Cascade:4
Boiler number 4 in the boiler cas-
cade.
Cascade:Screw
The boiler is charged via a screw
conveyor
conveyor. This screw conveyor is
switched by the external charge cab-
inet.
Cascade:Vacuum
The boiler is charged via a vacuum
module
module. The vacuum module is
switched by the boiler.
Charging
No automatic charging of the boiler
scheme:0
Only for boilers
Charging
Automatic charging with vacuum
scheme:2
module and discharge screw con-
veyor.
Charging
Vacuum module with external charg-
scheme:3
ing
Charging
Vacuum module with changeover
scheme:4
unit.
2 to 8 suction wands selectable.
Charging
Discharge screw conveyor
scheme:5
Only for boiler
Charging
External charging
scheme:6
Only for boiler
Charging
Screw conveyor and discharge
scheme:7
screw conveyor
Only for boiler
Charging
Screw conveyor and external charg-
scheme:8
ing.
Only for boiler
DHW:On the boil-
DHW heating is connected to the
er
boiler control unit.
DHW:On the mix-
DHW heating is connected to the ex-
er module
tension kit.
Codes
48 kW.
18 kW.
18 kW.
18 kW.
18 kW.
101