Viessmann VITOLIGNO 300-C Installation And Service Instructions Manual page 116

Pellet boiler 60 to 70 kw
Table of Contents

Advertisement

Codes
Code 2
(cont.)
Coding in the delivered condition
Primary air damper partial load
83:...
Do not change.
Primary air damper boiler start
84:...
Do not change.
Secondary air damper minimum
87:...
Do not change.
Automatically calibrate Lambda probe
F9:1
Settings for calibrating the Lambda
probe
Automatic start of Lambda probe
heating
Only manual calibration of Lamb-
da probe possible
Type O2 probe
FF:...
Lambda probe type
Charging
Available if code "Charging scheme", Hardware
group, is set.
Coding
Coding in the delivered condition
Maximum cycle, partial load
16:...
Max. feed cycle in partial load op-
eration
Only for boiler > 50 kW.
Combustion chamber fill time
1E:...
Feed screw conveyor runtime
Screw conveyor fill time
1F:...
Feed screw conveyor runtime.
Runtime for filling the feed screw
conveyor.
Fuel ash content
21:1.0
Fuel ash content
116
Possible change
83:...
to
83:...
84:...
to
84:...
87:...
to
87:...
F9:0
Lambda probe heating always on
Only manual calibration of Lambda
probe possible
F9:2
Automatic start of Lambda probe
heating
Automatic calibration of Lambda
probe
FF:0
Lambda probe type LSM 11
FF:1
Lambda probe type NGK
FF:2
Current signal 4 - 20 mA
FF:3
Wideband probe with BLS PCB
Possible change
16:...
Setting range in %
to
16:...
1E:...
Setting range in seconds
to
1E:...
1F:...
Setting range in seconds
to
1F:...
21:0.1
Setting range in percent
to
21:5.0