Screed drying function
This function enables screeds to be dried. For this,
observe the screed manufacturer's instructions.
When the screed drying function is enabled, the heat-
ing circuit pump is switched on and the flow tempera-
ture is held at the selected profile. After completion (30
days), the mixer circuit is automatically regulated using
the set parameters. EN 1264 must be observed. The
report to be provided by the heating contractor must
contain the following details regarding heat-up:
Heat-up data with respective flow temperatures
Max. flow temperature achieved
Operating state and outside temperature during
handover
Temperature profile 1 (EN 1264-4), code "F1:1"
ϑ/°C
50
40
30
20
10
1
5
10
15
20
Fig. 109
Temperature profile 2 (ZV parquet and flooring technology), code "F1:2"
ϑ/°C
50
40
30
20
10
1
5
10
15
20
Fig. 110
Temperature profile 3, code "F1:3"
ϑ/°C
50
40
30
20
10
1
5
10
15
20
Fig. 111
Temperature profile 4, code "F1:4"
ϑ/°C
50
40
30
20
10
1
5
10
15
20
Fig. 112
25
30
t/d
25
30
t/d
t/d
25
30
25
30
t/d
Various temperature profiles are adjustable via coding
address "F1".
The function continues after a power failure or after the
control unit has been switched off. "Heating" is started
when the screed drying function is finished or if code
"F1:0" is set manually.