Mitsubishi Electric MELSEC-A0J2H Series Handbook page 62

Table of Contents

Advertisement

3
I/O MODULES REPLACEMENT
(5) Specifications comparison between A0J2E-E24T and QY80
Specifications
Number of output points
Insulation method
Rated load voltage
Operating load voltage
range
Maximum load current
Maximum inrush current
Leakage current at OFF
Maximum voltage drop at
ON
OFFON
Response
time
ONOFF
Surge suppressor
Common terminal
arrangement
Operation indication
Fuse
Fuse blown indication
Protection function
Protection function reset
External connection
method
Applicable wire size
Voltage
External
supply
power
Current
Current consumption
External dimensions
Weight
3
- 21
A0J2E-E24T
24 points
Photocoupler
12VDC/24VDC
10.2 to 26.4VDC
0.8A/ point, 0.6A/ point
(60% ON, 55°C)
No restriction (Short protect)
1.0mA or less
1VDC (TYP.) 0.8A
1.5VDC (MAX.) 0.8A
0.5ms or less
1.5ms or less
(Rated load, resistance load)
Surge absorbing diode
8 points/common
(Common terminal: TB9, TB19,
TB29)
Available (Turning ON the output
turns LED ON)
None
Available (When a fuse blown
occurs, LED is lit, and a signal is
Available (overheat protection
and short circuit protection)
Automatic reset (by deactivating
protection function)
36-point terminal block
connector
(M3 × 6 screws)
2
0.75 to 2mm
12VDC/24VDC
(10.2VDC to 26.4VDC)
200mA
(24VDC, All points are ON.)
0.145A (TYP. All points are ON.)
0.08A (TYP. All points are ON.)
250(H) × 132(W) × 41(D) mm
98(H) × 27.4(W) × 90(D) mm
0.73kg
: Compatible,
QY80
Compatibility
16 points
Photocoupler
12VDC/24VDC
10.2 to 28.8VDC
0.5A/ point, 4A/common
4A 10ms or less
0.1mA or less
0.2VDC (TYP.) 0.5A
0.3VDC (MAX.) 0.5A
1ms or less
1ms or less
Zener diode
16 points/common
(Common terminal: TB17)
ON indication (LED)
6.7A (Not exchangeable)
(Fuse blown capacity: 50A)
output to the CPU)
None
18-point terminal block
(M3 × 6 screws)
2
0.3 to 0.75mm
core
(Outside diameter: 2.8mm or
less)
12VDC/24VDC
(10.2VDC to 28.8VDC)
(Ripple ratio within 5%)
20mA (During 24VDC)
0.17kg
: Partially changed, × : Incompatible
Precautions for replacement
When seventeen or more points
are used, use two QY80s.
The maximum load current per
point is smaller. Use caution on
selecting the load to use.
The inrush current value differs.
Use caution on selecting the load
to use.
The response times differ.
As the common changes from
three commons to a common,
wiring with a different voltage for
each common is not possible.
The QY80 has the fuse instead of
overheat and short circuit
protection function.
×
×
×
Wiring change is required.
×
The dimensions are different.