Advertisement

3
I/O MODULES REPLACEMENT
Specifications
External connection
method
Applicable wire size
Applicable solderless
terminal
Current consumption
External dimensions
Weight
*1
Connect the varistor exteriorly to reduce noise.
*2
Install a fuse for each external terminal point to prevent the burnout of the external devices and modules during load shorts.
A0J2E-E24R
36-point terminal block
connector (M3 × 6 screws)
2
0.75 to 2mm
(Outside diameter: 2.8mm or
1.25-3, 1.25-YS3A,
2-S3, 2-YS3A,
(Sleeved solderless terminals
V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
0.145A (TYP. All points are ON.
0.43A (TYP. All points are ON.)
250(H) × 132(W) × 41(D) mm
98(H) × 27.4(W) × 90(D) mm
0.75kg
: Compatible,
QY10
Compatibility
18-point terminal block
×
(M3 × 6 screws)
2
0.3 to 0.75mm
core
×
less)
R1.25-3
×
cannot be used.)
×
0.22kg
: Partially changed, × : Incompatible
Precautions for replacement
Wiring change is required.
Review current capacity since
current consumption is increased.
The dimensions are different.
3
- 18