3
I/O MODULES REPLACEMENT
Specifications
Mechanical life
Electrical life
OFFON
Response
time
ONOFF
External
Voltage
supply
power
(Relay coil
Current
driving
power)
3
- 35
A0J2-E28AR output
specifications
20 million times or more
Rated switching
voltage/current load
200,000 times or more
(COS=0.7) 100,000 times or
200VAC 0.4A, 240VAC 0.3A
(COS=0.7) 300,000 times or
200VAC 1.5A, 240VAC 1A
(COS=0.7) 200,000 times or
more
(COS=0.35) 100,000 times or
200VAC 0.75A, 240VAC 0.5A
(COS=0.35) 200,000 times or
more
(COS=0.35) 300,000 times or
24VDC 1A, 100VDC 0.1A
(L/R=7ms) 200,000 times or
more
(L/R=7ms) 100,000 times or
(L/R=7ms) 300,000 times or
10ms or less
12ms or less
24VDC±10%
Ripple voltage 4Vp-p or less
125mA
(24VDC. All points are ON.)
: Compatible,
QY10
Compatibility
20 million times or more
Rated switching
voltage/current load
100,000 times or more
200VAC 1.5A, 240VAC 1A
more
more
200VAC 1A, 240VAC 0.5A
more
200VAC 0.3A, 240VAC 0.15A
more
24VDC 1A, 100VDC 0.1A
more
24VDC 0.3A, 100VDC 0.03A
more
10ms or less
12ms or less
: Partially changed, × : Incompatible
Precautions for replacement
Reduce the exchange intervals of
the modules as Mechanical/
Electrical Life is cut to about half.
External supply power is not