Appendix 2.2 Performance Specifications Comparison - Mitsubishi Electric MELSEC-A0J2H Series Handbook

Table of Contents

Advertisement

Appendix 2.2 Performance specifications comparison

This section shows the performance specifications comparison between A0J2 series I/O modules and
interface modules of renewal tool for A0J2 described in Section 1.2.
(1) Specifications comparison between A0J2-E32A and interface module (SC-A0JQIF32A)
Specifications
A0J2-E32A input specifications
Number of input points
Insulation method
Rated input voltage
Rated input current
Operating voltage range
Maximum number of
simultaneous input
points
ON voltage/ON current
OFF voltage/OFF
current
Inrush current
Input impedance
OFFON
Response
time
ONOFF
Common terminal
arrangement
(Common terminal: TB17, TB34)
Operation indication
(Turning ON the input turns LED ON)
App
- 3
SC-A0JQIF32A input specifications Compatibility
32 points
Photocoupler
100 to 120VAC 50/60Hz
10mA (100VAC 60Hz)
85 to 132VAC (50/60Hz±5%)
100% (16 points/common)
simultaneously ON
80VAC or more/6mA or more
40VAC or less/4mA or less
Maximum 300mA,
Within 0.3ms (132VAC)
Approx. 10k (60Hz),
Approx. 12k (50Hz)
15ms or less (6ms TYP.)
35ms or less (16ms TYP.)
16 points/common
Available
32 points
Photocoupler
100 to 120VAC 50/60Hz
10mA (100VAC 60Hz)
85 to 132VAC (50/60Hz±5%)
*1
Refer to the derating chart.
80VAC or more/6mA or more
26VAC or less/1.7mA or less
Maximum 300mA,
Within 0.3ms (132VAC)
Approx. 10k (60Hz),
Approx. 12k (50Hz)
14ms or less
(11ms TYP.)
19ms or less
(13ms TYP.)
16 points/common
(Common terminal: TB17, TB34)
None
: Compatible,
: Partially changed, × : Incompatible
Precautions for replacement
Use it within the range shown in the
derating chart.
When the voltage of the external
supply power (module power supply) is
high, the rate of AC input simultaneous
ON becomes small.
OFF voltage/OFF current is smaller.
In combination with Q series input
module:
15ms or less (12ms TYP.)
In combination with Q series input
module:
20ms or less (14ms TYP.)
Operation indication can be checked
with Q series input module.
*2
*3
*3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec q series

Table of Contents