(3) Derating chart for the maximum number of simultaneous input points
(a) Input module on the programmable controller side
Check the number of simultaneous input points by referring to the derating chart of the selected Q
series input module.
Note that the maximum number of simultaneous input points is 100% (all points simultaneously ON)
when the QX41/QX41Y41P is selected because the applicable voltage range of the renewal tool for
A0J2 is 26.4VDC at maximum.
(b) Renewal tool for A0J2
The maximum number of simultaneous input points of the renewal tool for A0J2 (input module) has
the limitation depending on the external supply power (24VDC) that supplies the power to the
module. Use the module within the range shown in the derating chart in the performance
specifications comparison.
(4) Temperature derating for the triac output module
The output load current of the renewal tool for A0J2 (triac output module) has the limitation depending
on the ambient temperature in the environment where the module is used.
Use the module within the range shown in the temperature derating chart in the performance
specifications comparison.