(2) Specifications comparison between A0J2-E32D and interface module (SC-A0JQIF32D)
Specifications
A0J2-E32D input specifications
Number of input points
Insulation method
Rated input voltage
Rated input current
Operating voltage range
Maximum number of
simultaneous input
points
ON voltage/ON current
9.5VDC or more/2.6mA or more
OFF voltage/OFF
current
Input resistance
Input form
Sink input (Input current flows off.)
OFFON
Response
time
ONOFF
Common terminal
arrangement
(Common terminal: TB17, TB34)
Operation indication
(Turning ON the input turns LED ON)
App
- 5
SC-A0JQIF32D input specifications Compatibility
32 points
Photocoupler
12VDC/24VDC
Approx. 3mA/Approx. 7mA
10.2 to 26.4VDC
(Ripple ratio within 5%)
100% (16 points/common)
simultaneously ON
6VDC or less/1.0mA or less
Approx. 3.4k
Sink input (Input current flows off.)
10ms or less (6ms TYP.)
10ms or less (7.5ms TYP.)
16 points/common
Available
32 points
Photocoupler
12VDC/24VDC
Approx. 3mA/Approx. 7mA
10.2 to 26.4VDC
(Ripple ratio within 5%)
*1
Refer to the derating chart.
9.5VDC or more/2.6mA or more
6VDC or less/1.0mA or less
Approx. 3.3k
5ms or less (1ms TYP.)
5ms or less (1ms TYP.)
16 points/common
(Common terminal: TB17, TB34)
None
: Compatible,
: Partially changed, × : Incompatible
Precautions for replacement
Use it within the range shown in the
derating chart.
Input resistance is smaller.
In combination with Q series input
module:
*2
6ms or less (2ms TYP.)
In combination with Q series input
module:
*2
6ms or less (2ms TYP.)
Operation indication can be checked
with Q series input module.