Mitsubishi Electric MELSEC-A0J2H Series Handbook page 85

Table of Contents

Advertisement

3
I/O MODULES REPLACEMENT
(11)Specifications comparison between A0J2-E28DS and QX40+QY22
Specifications
Number of input points
Insulation method
Rated input voltage
Rated input current
Operating voltage range
Maximum number of
simultaneous input
points
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Input form
OFFON
Response
time
ONOFF
Common terminal
arrangement
Operation indication
Specifications
Number of output points
Insulation method
Rated load voltage
Maximum load voltage
Maximum load current
Minimum load voltage,
current
Maximum inrush current
Leakage current at OFF
Maximum voltage drop at
ON
OFFON
Response
time
ONOFF
Fuse rating
Fuse blown indication
Surge suppressor
A0J2-E28DS input
specifications
16 points
Photocoupler
12VDC/24VDC
Approx. 3mA/Approx. 7mA
10.2 to 26.4VDC
(Ripple ratio within 5%)
100% (16 points)
simultaneously ON
9.5VDC or more/2.6mA or more
19VDC or more/3mA or more
6VDC or less/1.0mA or less
11VDC or less/1.7mA or less
Approx. 3.4k
Sink input
(Input current flows off.)
1ms/5ms/10ms/20ms/70ms or
10ms or less (6ms TYP.)
1ms/5ms/10ms/20ms/70ms or
10ms or less (7.5ms TYP.)
16 points/common
(Common terminal: TB17)
Available (Turning ON the input
turns LED ON)
A0J2-E28DS output
specifications
12 points
Photocoupler
100 to 240VAC, 40 to 70Hz
264VAC
0.6A/point, 2.4A/common
24VAC 100mA
100VAC 10mA
240VAC 10mA
20A 10ms or less
8A 100ms or less
1.5mA (120VAC 60Hz)
3mA (240VAC 60Hz)
1.5V or less
(100 to 600mA)
1.8V or less
(100mA or less)
2.0V or less
(10 to 50mA)
1ms or less
0.5 cycle + 1ms or less
(Rated load, resistance load)
High speed type fuse 3.2A
(1/common) HP-32
Available (When a fuse blown
occurs, LED is lit, and a signal is
output to the CPU)
CR absorber
(0.022µF + 47)
: Compatible,
QX40
Compatibility
16 points
Photocoupler
24VDC
Approx. 4mA
20.4 to 28.8VDC
(Ripple ratio within 5%)
100% simultaneously ON
Approx. 5.6k
Positive common
less
(Set it with CPU parameter.)
Initial setting is 10ms.
less
(Set it with CPU parameter.)
Initial setting is 10ms.
16 points/common
(Common terminal: TB17)
ON indication (LED)
QY22
Compatibility
16 points
Photocoupler
100 to 240VAC
50/60Hz±5%
264VAC
0.6A/point, 4.8A/common
24VAC 100mA
100VAC 25mA
240VAC 25mA
20A 1 cycle or less
1.5mA or less
(During 120V 60Hz)
3mA or less
(During 240V 60Hz)
1.5V or less
1ms or less
1ms + 0.5 cycle or less
None
CR absorber
*1
: Partially changed, × : Incompatible
Precautions for replacement
*2
12VDC cannot be used.
Rated input current is smaller.
*2
12VDC cannot be used.
*2
12VDC cannot be used.
*2
12VDC cannot be used.
*3
Input resistance is greater.
The name is different, but the
specificaton is equal.
Input response time of the
parameter must be used at the
initial value (10ms).
Precautions for replacement
The frequency will be low. Check
the specifications of external
devices.
The minimum load current is
greater. Use caution on selecting
the load to use.
×
*4
The fuse is not built in.
×
3
*3
- 44

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec q series