Mitsubishi Electric MELSEC-A0J2H Series Handbook page 208

Table of Contents

Advertisement

(6) Specifications comparison between A0J2-E24T and interface module (SC-A0JQIF24T)
Specifications
A0J2-E24T output specifications
Number of output points
Insulation method
Rated input voltage
Operating voltage range
Maximum switching
current
Maximum inrush current
Leakage current at off
Maximum voltage drop
at on
OFFON
Response
time
ONOFF
External
Voltage
supply
power
Current
Surge suppressor
Common terminal
arrangement
(Common terminal: TB9, TB19, TB29)
Operation indication
(Turning ON the output turns LED ON)
Fuse rating
Fuse blown indication
App
- 13
24 points
Photocoupler
12VDC/24VDC
10.2 to 30VDC
0.5A/point, 4A/common
4A 10ms or less
0.1mA or less
0.9VDC(TYP.)0.5A
1.5VDC(MAX.)0.5A
2ms or less
2ms or less (Resistance load)
12VDC/24VDC
(10.2VDC-30VDC)
23mA (TYP.24VDC
8 points are ON/common.)
Varistor (52V-62V)
8 points/common
(Common terminal: TB9, TB19, TB29)
Available
None
SC-A0JQIF24T output
Compatibility
specifications
24 points
Photocoupler
12VDC/24VDC
10.2 to 30VDC
0.5A/point, 4A/common
4A 10ms or less
0.1mA or less
0.9VDC(TYP.)0.5A
0.8VDC(MAX.)0.5A
1ms or less
2ms or less (Resistance load)
12VDC/24VDC
(10.2VDC-30VDC)
5mA (TYP.24VDC
8 points are ON/common.)
Varistor (50.4V-61.6V)
8 points/common
None
6.7A (Cannot be changed.)
(Fuse blown capacity: 50A)
: Compatible,
: Partially changed, × : Incompatible
Precautions for replacement
In combination with Q series output
module:
*1
2ms or less
In combination with Q series output
module:
3ms or less (Resistance load)
Operation indication can be checked
with Q series output module.
*1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec q series

Table of Contents