Rack Requirements for an ACX5000 Router

All ACX5000 routers are designed to be installed on four-post racks. The ACX5096 can also be installed
on two-post racks.
Rack requirements consist of:
Rack type
Mounting bracket hole spacing
Rack size and strength
Table 28 on page 86
provides the rack requirements and specifications for an ACX5000 router.
Table 28: Rack Requirements for an ACX5000 Router
Rack Requirement
Rack type (all router
models)
Rack type (ACX5096
only)
Mounting bracket hole
spacing (all router
models)
Guidelines
Use a four-post rack that provides bracket holes or hole patterns spaced at 1 U (1.75 in.
or 4.45 cm) increments and that meets the size and strength requirements to support the
weight.
A U is the standard rack unit defined in Cabinets, Racks, Panels, and Associated Equipment
(document number EIA-310–D) published by the Electronics Industry Association.
Use a two-post or four-post rack that provides bracket holes or hole patterns spaced at
1 U (1.75 in. or 4.45 cm) increments and that meets the size and strength requirements
to support the weight.
The holes in the mounting brackets are spaced at 1 U (1.75 in. or 4.45 cm), so that the
router can be mounted in any rack that provides holes spaced at that distance.