Chassis Physical Specifications For An Acx5000 Router - Juniper ACX5048 Hardware Manual

Universal metro router
Hide thumbs Also See for ACX5048:
Table of Contents

Advertisement

For the cooling system to function properly, the airflow around the chassis must be unrestricted. See
"Cooling System and Airflow in an ACX5000 Router" on page 60
through the chassis.
If you are mounting an ACX5000 router in a rack or cabinet with other equipment, ensure that the
exhaust from other equipment does not blow into the intake vents of the chassis.
Leave at least 24 in. (61 cm) both in front of and behind the ACX5000 router. For service personnel to
remove and install hardware components, you must leave adequate space at the front and back of the
router. NEBS GR-63 recommends that you allow at least 30 in. (76.2 cm) in front of the rack or cabinet
and 24 in. (61 cm) behind the rack or cabinet.
SEE ALSO
Rack-Mounting and Cabinet-Mounting Warnings | 170

Chassis Physical Specifications for an ACX5000 Router

The ACX5000 router chassis is a rigid sheet-metal structure that houses the hardware components.
Table 25 on page 82
summarizes the physical specifications of an ACX5000 router.
Table 25: Physical Specifications for an ACX5000 Router Chassis
Router Model
Height
ACX5048
1.72 in. (4.3 cm)
ACX5096
3.46 in. (8.8 cm)
SEE ALSO
Mounting an ACX5000 Router in a Rack or Cabinet | 103
ACX5048 and ACX5096 Installation Overview | 101
Removing an ACX5000 Router from a Rack or Cabinet | 143
Width
Depth
17.36 in. (44.1 cm)
20.48 in. (52 cm)
17.36 in. (44.1 cm)
22.44 in. (57 cm) (not
including handles for Fans
and PSUs)
for more information about the airflow
Weight
With FRUs installed:
21.8 lbs (9.8 kg)
With FRUs installed: 32 lbs
(14.5 kg)
82