Panasonic Elite Big PAC-i S-200PE3E5B Technical Data & Service Manual page 99

Dc inverter
Hide thumbs Also See for Elite Big PAC-i S-200PE3E5B:
Table of Contents

Advertisement

1-1. How to Set on PC Board
1. Turn off the power breaker to halt the supply of electricity to the PC board.
2. Open the lid of the electrical component box and confirm the location where the Select switch on the indoor unit control PCB is
placed. (Fig. 1-12-2-1-3)
3. Set the On/Off switches in the Off position which are now set in the On position.
Select the positions of the Select SW001 switches respectively to make the desired external static pressure settings referring to
the Table 1-12-2-1-2.
Table 1-12-2-1-2 External static pressure SW setting
External static pressure at the
time of rated airflow volume
200
250
180Pa
200Pa
120Pa
130Pa
75Pa
75Pa
1-2. Operating the Timer Remote Controller (CZ-RTC4)
How to set the external static pressure
1. Press and hold down the
simultaneously for 4 or more seconds. (
Unit No., Item Code and Detailed Data will blink on
the LCD display.)
2. The indoor unit numbers in the group control will be
sequentially displayed whenever the Unit Select button
is pressed
.
Only the fan motor for the selected indoor unit will operate
during this time.
3. Specify the "
" item code by pressing the
buttons for the temperature setting buttons and confirm
the values. ("
" set at shipment)
4. Press the
buttons for the time to amend the
/
values for the set data. Refer to Table 1-12-2-1-3 and
Fig. 1-12-2-1-4 and select a value "
"
".
5. Press the
button.
The display will stop blinking and remain illuminated.
6. Press the
button. The fan motor will stop operating
and the LCD display will return to the normal stop mode.
SW001
TP6
TP3
TP1
ON
1
2
3
ON
1
2
3
ON
1
2
3
,
and
buttons
, the
/
/
/
", "
" or
1-12-2-1-8
SW001
ON
1
2
3
Setting at
shipment
Table 1-12-2-1-3 Setting the external static pressure
Indoor unit
200
External static pressure of the rated
air flow volume
180 Pa
120 Pa
75 Pa
1
3
A
6
NOTE:
Failure to set this parameter may result in
decreased airflow and condensation.
Indoor Unit control PC board
SW001
ON
1
2
3
Fig. 1-12-2-1-3
Item code
250
200 Pa
130 Pa
75 Pa
1
4
°
1
°
4
2
5
1
1