Panasonic Elite Big PAC-i S-200PE3E5B Technical Data & Service Manual page 313

Dc inverter
Hide thumbs Also See for Elite Big PAC-i S-200PE3E5B:
Table of Contents

Advertisement

Auto Address
Set the Auto Address for each O/D unit no. (outdoor unit number) Select the O/D unit no. for Auto Address.
AC
1. Press
for 4 seconds or longer.
ADR
• "
" starts blinking and the setting screen is displayed.
2. Press
to select the unit number (O/D unit no.)
from 1 to 30.
3. Press
to set the Auto Address.
4. Press
to check the Auto Address status.
(Refer to the following table for the Auto Address status.)
• Proceed to step 5 when the status is "Completion" or "Error" .
• If "Running" keeps for 10 minutes or longer, check the unit number.
Auto
Buzzer
Address
of the
OPERATION
Status
receiver
Running
2 times
Completion
1 time
Error
5 times
: ON (Illuminated), ◎ Blinking (0.5 seconds interval)
: OFF,
5. Press
for 4 seconds or longer to exit the Auto Address setting.
• Auto Address setting is canceled while running or error occurring.
Set the Auto Address again after resolve the error cause if an error occurs.
• Set Auto address after all units are turned on and 90 seconds or more have passed.
• Operate the units after Auto address is set and 90 seconds or more have passed.
Indication lamp on the receiver
TIMER
STANDBY
-
-
2
1
-
8-37
Address
4
3
5
8