Panasonic S-200PE1E8 Technical Data & Service Manual

Panasonic S-200PE1E8 Technical Data & Service Manual

Dc inverter, r410a
Hide thumbs Also See for S-200PE1E8:
Table of Contents

Advertisement

TECHNICAL DATA

&
SERVICE MANUAL
Indoor Unit
Outdoor Unit
Type E1
S-200PE1E8, S-250PE1E8
U-200PE1E8, U-250PE1E8
SM830194-03
.
REFERENCE NO
85464849294003

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic S-200PE1E8

  • Page 1: Technical Data

    TECHNICAL DATA & SERVICE MANUAL Indoor Unit Outdoor Unit Type E1 S-200PE1E8, S-250PE1E8 U-200PE1E8, U-250PE1E8 SM830194-03 REFERENCE NO 85464849294003...
  • Page 2: Special Precautions

    IMPORTANT! • Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire Please Read Before Starting hazard. • Provide a power outlet to be used exclusively for each This air conditioning system meets strict safety and unit, and a power supply disconnect, circuit breaker and operating standards.
  • Page 3 When Connecting Refrigerant Tubing Others • When performing piping work do not • Do not touch the air inlet or CAUTION the sharp aluminum fins of the mix air except for specified refrigerant outdoor unit. You may hurt. (R410A) in refrigeration cycle. It causes capacity down, and risk of •...
  • Page 4: Check Of Density Limit

    Check of Density Limit The standards for minimum room volume are as follows. (1) No partition (shaded portion) The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set limit. The refrigerant (R410A), which is used in the air conditioner, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to protect the ozone layer.
  • Page 5: Table Of Contents

    —— CONTENTS —— Section 1. SPECIFICATIONS ....................1-1. Unit Specifications ....................... 1-2. Major Component Specifications ..................1-3. Other Component Specifications ..................1-4. Dimensional Data ....................... 1-10 1-5. Refrigerant Flow Diagram ....................1-13 1-6. Operating Range ........................ 1-13 1-7. Capacity Correction Graph According to Temperature Condition ........ 1-14 1-8.
  • Page 6 Section 6. OUTDOOR UNIT MAINTENANCE REMOTE CONTROL........6-1. Overview ..........................6-2. Functions..........................6-3. Normal Display Operations and Functions ............... 6-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures..6-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History ..6-6.
  • Page 7: Section 1. Specifications

    1. SPECIFICATIONS 1-1. Unit Specifications..................... 1-2. Major Component Specifications ................1-3. Other Component Specifications ................1-4. Dimensional Data ..................... 1-10 1-5. Refrigerant Flow Diagram ..................1-13 1-6. Operating Range ...................... 1-13 1-7. Capacity Correction Graph According to Temperature Condition ..... 1-14 1-8.
  • Page 8: Unit Specifications

    Single-Type 1-1. Unit Specifications High Static Pressure Ducted Type S-200PE1E8 / U-200PE1E8 Indoor Unit S-200PE1E8 MODEL No. Outdoor Unit U-200PE1E8 Indoor Unit 220-230-240V, 50/60Hz, single-phase POWER SOURCE Outdoor Unit 380-400-415V, 50/60Hz, 3-phase PERFORMANCE Cooling Heating 20.0 [6.0~22.4] 22.4 [6.0~25.0] Capacity [min~max]...
  • Page 9 Single-Type 1-1. Unit Specifications High Static Pressure Ducted Type S-250PE1E8 / U-250PE1E8 Indoor Unit S-250PE1E8 MODEL No. Outdoor Unit U-250PE1E8 Indoor Unit 220-230-240V, 50/60Hz, single-phase POWER SOURCE Outdoor Unit 380-400-415V, 50/60Hz, 3-phase PERFORMANCE Cooling Heating 25.0 [6.0~28.0] 28.0 [6.0~31.5] Capacity [min~max] BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]...
  • Page 10: Major Component Specifications

    1-2. Major Component Specifications (A) Indoor Units High Static Pressure Ducted Type S-200PE1E8 MODEL No. S-200PE1E8 Source 220 - 230 - 240V, single-phase, 50/60Hz Controller P.C.B. Ass'y CR-UXRP71B-P (Microprocessor) Fan (Number...diameter) Centrifugal (2...ø220) Fan motor Model...Nominal output KFC4X-201B5P...180W Power source 220 - 230 - 240V, single-phase, 50Hz No.
  • Page 11 1-2. Major Component Specifications (A) Indoor Units High Static Pressure Ducted Type S-250PE1E8 MODEL No. S-250PE1E8 Source 220 - 230 - 240V, single-phase, 50Hz Controller P.C.B. Ass'y CR-UXRP71B-P (Microprocessor) Fan (Number...diameter) Centrifugal (2...ø250) Fan motor Model...Nominal output KFC4X-401B3P...400W Power source 220 - 230 - 240V, single-phase, 50Hz No.
  • Page 12 1-2. Major Component Specifications (B) Outdoor Units U-200PE1E8 MODEL No. U-200PE1E8 Source 380-400-415V, 3-phase, 50/60Hz Controller P.C.B. Ass'y CR-C906VH8P (Microprocessor) Control circuit fuse Compressor Model..number C-9RVN273H0K Source 246V (DC) / 3-phase / 60Hz (Inverter drive) Nominal output 4,200 Compressor oil 1,400 C –...
  • Page 13 1-2. Major Component Specifications (B) Outdoor Units U-250PE1E8 MODEL No. U-250PE1E8 Source 380-400-415V, 3-phase, 50/60Hz Controller P.C.B. Ass'y CR-C906VH8P (Microprocessor) Control circuit fuse Compressor Model..number C-9RVN393H0U Source 282V (DC) / 3-phase / 60Hz (Inverter drive) Nominal output 5,500 Compressor oil 1,900 C –...
  • Page 14: Other Component Specifications

    1-3. Other Component Specifications Outdoor Units U-200PE1E8 MODEL No. Outdoor Unit U-200PE1E8 Power Transformer – Rated – Source VAC, Hz – – Secondary – Coil resistance Ω – Thermal cut off temperature Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4 KTM-35D-S1, DTN-C532G3H Resistance kΩ...
  • Page 15 1-3. Other Component Specifications Outdoor Units U-250PE1E8 MODEL No. Outdoor Unit U-250PE1E8 Power Transformer – Rated – Source VAC, Hz – – Secondary – Coil resistance Ω – Thermal cut off temperature – Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4 KTM-35D-S1, DTN-C532G3H Resistance kΩ...
  • Page 16: Dimensional Data

    1-4. Dimensional Data (A) Indoor Units: High Static Pressure Ducted Type S-200PE1E8 S-250PE1E8 1170 (Suspension bolt pitch) 4 - 37×12 (Hole for suspension bolt) 1100 1222 1-10...
  • Page 17: Dimensional Data

    1-4. Dimensional Data (B) Outdoor Unit: U-200PE1E8 Unit: mm Mounting hole (4-R6.5), anchor bolt : M10 Refrigerant tubing (liquid tube), flared connection (ø9.52) Refrigerant tubing (gas tube), flared connection (ø19.05) Refrigerant tubing port Electrical wiring port (ø16) 2 x ø32 holes (holes for drain) Electrical wiring port (ø19) Of the 4 ø32 holes , use 1 of the 2 holes Electrical wiring port (ø29)
  • Page 18 1-4. Dimensional Data (B) Outdoor Unit: U-250PE1E8 Unit: mm Mounting hole (4-R6.5), anchor bolt : M10 Refrigerant tubing (liquid tube), flared connection (ø12.7) Refrigerant tubing (gas tube), flared connection (ø19.05) Refrigerant tubing port Electrical wiring port (ø16) 2 x ø32 holes (holes for drain) Electrical wiring port (ø19) Of the 4 ø32 holes , use 1 of the 2 holes Electrical wiring port (ø29)
  • Page 19: Refrigerant Flow Diagram

    1-5. Refrigerant Flow Diagram Cooling cycle Heating cycle Outdoor Unit : U-200PE1E8 Indoor Unit : S-200PE1E8 Accumulator Accumulator Compressor Strainer Solenoid Gas line valve service valve (3/4") High pressure ø25.4 (brazing) switch Heat exchanger Check valve 4-way valve Heat exchanger...
  • Page 20: Capacity Correction Graph According To Temperature Condition

    1-7. Capacity Correction Graph According to Temperature Condition U-200PE1E8 / U-250PE1E8 (For 50 Hz and 60 Hz) Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) Indoor air intake temp (WB) °C Indoor air intake temp ( °C °C °C 22WB 19WB...
  • Page 21: Noise Criterion Curves

    1-8. Noise Criterion Curves High Static Pressure Ducted Type Strong Weak MODEL : S-200PE1E8 : S-250PE1E8 MODEL SOUND LEVEL SOUND LEVEL : STRONG 48 dB(A) : STRONG 50 dB(A) CONDITION WEAK 45 dB(A) WEAK 48 dB(A) CONDITION : Under the unit 1.5 m...
  • Page 22 1-8. Noise Criterion Curves Standard (B) Outdoor Unit Quiet mode COOLING MODEL : U-200PE1E8 : U-200PE1E8 MODEL : 72 dB(A) SOUND LEVEL : STANDARD 57 dB(A) SOUND : Cooling QUIET MODE 50 dB(A) POWER LEVEL CONDITION : 1 m in front at height of 1.5 m NC-70 NC-70 NC-60...
  • Page 23 1-8. Noise Criterion Curves Standard (B) Outdoor Unit Quiet mode COOLING MODEL : U-250PE1E8 : U-250PE1E8 MODEL : 72 dB(A) SOUND SOUND LEVEL : STANDARD 57 dB(A) : Cooling POWER LEVEL QUIET MODE 50 dB(A) CONDITION : 1 m in front at height of 1.5 m NC-70 NC-70 NC-60...
  • Page 24: Electrical Wiring

    14 mm 96 m 20 A Indoor unit (B) Power supply Time delay fuse or circuit capacity 2.5 mm S-200PE1E8 Max. 50/30 m 10/16 A S-250PE1E8 Control wiring (C) Inter-unit (between outdoor (D) Remote control wiring and indoor units) control wiring 0.75 mm...
  • Page 25 Wiring System Diagrams Indoor unit Power supply* Outdoor unit (3-phase) 220 – 240 V ~50/60 Hz INV unit Power supply Ground Remote 380 – 415 V, 3N, ~ 50/60 Hz controller Ground Ground * Regarding S-250PE1E8, the power supply is 220-240V, 50Hz only.
  • Page 26 (3) Use shielded wires for inter-unit control wiring (c) and ground the shield on both sides, otherwise misoperation from noise my occur. (Fig. 1-2) Connect wiring as shown in Wiring System Diagram.” Shielded wire Ground Ground Fig. 1-2 (4) Use the standard power supply cables for Europe (such as H05RN-F or H07RN-F which conform to CENELEC (HAR) rating specifications) or use the cables based on IEC standard.
  • Page 27 Wiring sample Outdoor Unit Use this screw when connecting Use this screw when connecting to ground for the unit control line. to ground for the unit control line. Earth Earth Power Supply Unit Control Line Power Supply Unit Control Line Use this screw when connecting to ground for the unit control line.
  • Page 28: Installation Instructions

    1-10. Installation Instructions Outdoor Unit Tubing Length Single type During tubing work, try to make both the tubing length (L) Single and the difference in elevation (H1) as short as possible. Refer to Table 1-1. Main tubing L Table 1-1 Tubing Data for Models (Single) Models U-200PE1E8 U-250PE1E8...
  • Page 29: Check Of Limit Density

    This unit requires no additional refrigerant charge up to tubing length 30 m. In case CAUTION of more than 30 m, additional refrigerant charge is required. Refer to Table 1-1. In case of multi type installation, indoor units should be installed within the same room.
  • Page 30: Selecting The Installation Site

    3. SELECTING THE INSTALLATION SITE CAUTION When moving the unit during or after unpacking, make sure to lift it by holding its lifting lugs. Do not exert any pressure on other parts, especially the refrigerant piping, drain piping and flange parts. If you think the humidity inside the ceiling might exceed 30°C and RH 80%, reinforce the insulation on the unit body.
  • Page 31 Installation space Install the outdoor unit with a sufficient space around the outdoor unit for operation and maintenance. (1) Obstructions on the left side, right side and rear side (Front side and above the unit are opened). (Fig. 1-10) * Necessary space is required to unscrew on the rear side for maintenance and if a sufficient maintenance space is provided on the rear side (40 cm), the space of over 15 cm is enough at the right side.
  • Page 32 Air Discharge Chamber for Top Discharge Air discharge Be sure to install the air discharge chamber in the field when: It is difficult to keep a space of min. 1 m between the air discharge outlet and an obstacle. The air discharge outlet is facing to the sidewalk and discharged hot air annoys the passers-by.
  • Page 33: Dimensions Of Air-Discharge Chamber

    4. Dimensions of Air-Discharge Chamber : In snowy regions, if there is concern that snow may enter the air discharge chamber, remove the base of the chamber before using. Unit: mm Reference diagram for U-200PE1E8 / U-250PE1E8 Air discharge support Air intake Downward, Left side installation fi...
  • Page 34 Reference diagram for downward left side installation fi xture (fi eld supply) : Unit: mm 2-ø3.3 protrusion hole (reverse side) Reference diagram for downward right side installation fi xture (fi eld supply) : Unit: mm 2-ø3.3 protrusion hole (reverse side) Cyclic bending 1-28...
  • Page 35 Reference diagram for downward center side installation fi xture (fi eld supply) : Unit: mm Cyclic bending 32.5 (495) 32.5 Same on reverse side (135) 1-29...
  • Page 36 Reference diagram for upward left side installation fi xture (fi eld supply) : Unit: mm 10.5 145.5 Reference diagram for upward right side installation fi xture (fi eld supply) : Unit: mm 10.5 135.5 1-30...
  • Page 37 Reference diagram for upward left side installation fi xture (fi eld supply) : Unit: mm 2-ø3.3 protrusion hole (reverse side) 561.5 Reference diagram for upward right side installation fi xture (fi eld supply) : Unit: mm 2-ø3.3 protrusion hole (reverse side) Cyclic bending 1-31...
  • Page 38 Reference diagram for air-discharge chamber (fi eld supply) The models of U-200PE1E8 / U-250PE1E8 with Air-Discharge Chamber Required space around outdoor unit If the air discharge chamber is used, the space shown below must be secured around the outdoor unit. If the unit is used without the required space, a protective device may activate, preventing the unit from operating.
  • Page 39: Dimensions Of Wind-Proof Duct

    5. Dimensions of Wind-proof Duct : In snowy regions, if there is concern that snow may enter the wind-proof duct, remove the base of the chamber before using. Reference diagram for U-200PE1E8 / U-250PE1E8 Air intake Unit: mm discharge discharge Air discharge discharge discharge...
  • Page 40: Dimensions Of Snow-Proof Duct

    6. Dimensions of Snow-proof Duct : Reference diagram for U-200PE1E8 / U-250PE1E8 (295) Unit: mm Air Intake Air discharge (227) (303) Air discharge Air discharge Air Intake Reference diagram for snow-proof duct (fi eld supply) : Unit: mm Unit top, snow-proof duct Unit right side Unit left side Unit front side...
  • Page 41 Reference diagram for snow-proof duct - 1 Space requirements for setting - (1) The models of U-200PE1E8 / U-250PE1E8 with snow-proof duct Unit: mm [Obstacle to the rear of unit] [Obstacle to the front of unit] Top is open: Top is open: Single-unit installation (2) Obstacles on both sides Single-unit installation M i n .
  • Page 42 Reference diagram for snow-proof duct - 2 Space requirements for setting - (2) The models of U-200PE1E8 / U-250PE1E8 with snow-proof duct [Obstacles to the front and rear of unit] The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit.
  • Page 43: How To Install The Outdoor Unit

    7. HOW TO INSTALL THE OUTDOOR UNIT 1. Installing the Outdoor Unit For 8 and 10 HP unit Unit: mm Use concrete or a similar material to make the base, and ensure good drainage. 2- o32 Specified drain port Ordinarily, ensure a base height of 5 cm or more. Air Intake If a drain pipe is used, or for use in cold-weather regions, ensure a height of 15 cm or more at the feet...
  • Page 44: Indoor Unit

    Indoor Unit 8. SELECTING THE INSTALLATION SITE CAUTION When moving the unit during or after unpacking, make sure to lift it by holding its lifting lugs. Do not exert any pressure on other parts, especially the refrigerant piping, drain piping and flange parts. If you think the humidity inside the ceiling might exceed 30°C and RH 80%, reinforce the insulation on the unit body.
  • Page 45: How To Install The Indoor Unit

    9. HOW TO INSTALL THE INDOOR UNIT High Static Pressure Ducted Type (E1 Type) 1. Required Minimum Space for Installation and Service (200, 250 Types) Unit: mm The installation instructions that come with the indoor unit describe how to use it in combination with the U-200PE1E8 1170 Min.
  • Page 46 2. Suspending the Indoor Unit Depending on the ceiling type: Insert suspension bolts as shown in Fig. 1-21 Use existing ceiling supports or construct a suitable support as shown in Fig. 1-22. Hole-in-anchor Concrete Insert Hole-in-plug Ceiling tiles Ceiling support Suspension bolt (M10 or 3/8”) (field supply) Fig.
  • Page 47 The type 200 indoor unit comes with a tube connector Remove the ø 12.7 flare nut from the liquid tubing of that is for liquid tubing. Configure as shown in the the indoor unit and use it. illustration and connect it. When flaring the tube, put the flare nut onto it first To indoor unit and then flare it.
  • Page 48: How To Process Tubing

    1-11. HOW TO PROCESS TUBING The liquid tubing side is connected by a flare nut, and the gas tubing side is connected by brazing. 1. Connecting the Refrigerant Tubing Use of the Flaring Method Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes that run between indoor and outdoor units.
  • Page 49 Caution Before Connecting Tubes Tightly Apply a sealing cap or water-proof tape to prevent dust or water from entering the tubes before they are used. Be sure to apply refrigerant lubricant (ether oil) to the Apply refrigerant lubricant. inside of the flare nut before making piping connections. This is effective for reducing gas leaks.
  • Page 50 3. Out Rear 4. Out Bottom Flare Process Flare Process The ø25.4 gas main will not pass easily into the opening for coolant pipes in the pipe cover, so make sure you connect the ø25.4 pipe with the ø19.05 pipe outside of the outdoor unit. (2) Tightly connect the indoor-side refrigerant tubing Torque wrench extended from the wall with the outdoor-side tubing.
  • Page 51 In order to prevent damage to the flare caused by over-tightening of the flare nuts, use the table above as a guide when tightening. When tightening the flare nut on the liquid tube, use an adjustable wrench with a nominal handle length of 200 mm.
  • Page 52 4. Taping the Tubes (1) At this time, the refrigerant tubes (and electrical wiring if local codes permit) should be taped together with armoring tape in 1 bundle. To prevent condensation Inter-unit Gas tube Liquid tube control wiring from overflowing the drain pan, keep the drain hose separate from the refrigerant tubing.
  • Page 53: Leak Test, Evacuation And Additional Refrigerant Charge

    1-12. LEAK TEST, EVACUATION AND ADDITIONAL REFRIGERANT CHARGE Perform an air-tightness test for this package A/C. Check that there is no leakage from any of the connections. Air and moisture in the refrigerant system may have undesirable effects as indicated below. pressure in the system rises operating current rises cooling (or heating) efficiency drops...
  • Page 54 2. Evacuation Be sure to use a vacuum pump that includes a function for prevention of back-flow, in order to prevent back-flow of pump oil into the unit tubing when the pump is stopped. Manifold valve Perform vacuuming of the indoor unit and tubing. Connect the vacuum pump to the gas tube valve and apply vacuum at a pressure of –101kPa (–755 mmHg, 5 Torr) or below.
  • Page 55: How To Select Ahu System

    1-13. How to select AHU system AHU system selection guideline System lineup Capacity Outdoor combination Connectable AHU-kit combination 20 kW U-200PE1E8 CZ-280PAH1 25 kW U-250PE1E8 CZ-280PAH1 * Single connection type only * Mix connection with standard indoor units is not allowed. * The system is applicable to the above models.
  • Page 56 Installation Installation of Strainer (Field supplied) Attach the strainer to the side of the outdoor unit for Gas & Liquid piping. (See the “System Overview” on previous page.) Thermistor for Liquid pipe and Heat exchanger pipe middle Liquid pipe thermistor Attach the liquid pipe thermistor Cover the thermistor Cover the aluminum...
  • Page 57 Blower operation signal and protection signal Blower signal output Power supply Minimum applicable load DC 5 V, 1 mA Maximum applicable load AC 230 V, 2 A X1 : Relay (field supply) Blower protect input SW 1 : operation command (field supply) AC 220 ~240 V, 0.1 A Limitation of AHU When the AHU is selected, there are some limitations.
  • Page 58 Restriction on the number of passes of the heat exchanger hairpin Minimum number of passes = Number of steps × Distance between tube sheets × Number of rows × 1.5 ×10 <For example> Number of steps Distance between tube sheets 1000 [mm] Number of rows Minimum number of passes = 12 ×...
  • Page 59: Section 2. Test Run

    2. TEST RUN 2-1. Preparing for Test Run ..........................2-2 E1 Type 2-2. Caution ............................... 2-3. Test Run Procedure ........................... 2-4. Items to Check Before the Test Run ......................2-5. Test Run Using the Remote Controller ...................... 2-6. Precautions ............................... 2-7.
  • Page 60: Preparing For Test Run

    2-1. Preparing for Test Run Before attempting to start the air conditioner, check the following: (1) All loose matter is removed from the cabinet especially steel filings, bits of wire, and clips. (2) The control wiring is correctly connected and all (Power must be turned ON at least electrical connections are tight.
  • Page 61: Items To Check Before The Test Run

    2-4. Items to Check Before the Test Run (1) Turn the remote power switch ON at least 12 hours in advance in order to energize the crankcase heater. Fully open the closed valves on the liquid-tube and gas-tube sides. 2-5. Test Run Using the Remote Controller (1) Press and hold the remote controller button for 4 seconds or longer.
  • Page 63: System Control

    2-8. System Control System control refers to the link wiring connection for control of simultaneous-operation multi systems, group control, and main-sub remote controller control. 2-8-1. Basic wiring diagram Single type Be careful to avoid miswiring when connecting the wires. (Miswiring will damage the units.) (for 3-phase outdoor unit) System address rotary switch Ground...
  • Page 64 2-8-2. Setting the outdoor unit system addresses For basic wiring diagram (Set the system address: 1) Outdoor unit control PCB 8 – 10 HP OC (CN500, BLU) EMG (CN502, BRN) 63PH (CN027, WHT) System address rotary switch SILENT (CN037, WHT) FUSE (0.5A, F500) (Set to “0”...
  • Page 65 2-8-4. Indicating (marking) the indoor and outdoor unit combination number Indicate (mark) the number after automatic address setting is completed. (1) So that the combination of each indoor unit can be easily checked when multiple units are installed, ensure that the indoor and outdoor unit numbers correspond to the system address number on the outdoor unit control PCB, and use a magic marker or similar means which cannot be easily erased to indicate the numbers in an easily visible location on the indoor units (near the indoor unit nameplates).
  • Page 66: Test Run Procedure

    2-9. Test Run Procedure Recheck the items to check before the test run. (See 2-10) Check the combination (wiring) of indoor and outdoor units. (See 2-15) Is system “single-type”? (1 indoor unit is connected to 1 outdoor unit) Are multiple outdoor units used? (See 2-15-2) Turn ON the indoor and...
  • Page 67: Items To Check Before The Test Run

    2-10. Items to Check Before the Test Run Turn the remote power switch ON at least 12 hours in advance in order to energize the crankcase heater. Fully open the closed valves on the liquid-tube and gas-tube sides. 2-11. Preparation for Test Run 2-11-1.
  • Page 68: Test Run

    2-12. Test Run Using the control unit (1) Change the indoor control unit switch from “ON” “TEST”. Indoor control unit switch (The outdoor unit will not operate for 3 minutes after the power is turned ON and after operation is stopped.) (2) All the indicator lamps blink while the test run is in progress.
  • Page 69: Table Of Self-Diagnostic Functions And Corrections

    2-14. Table of Self-Diagnostic Functions and Corrections Cause Wired remote controller Indoor unit Group connection Correction display receiver lamp 1:1 connection (Single type) (Simultaneous multi (Field supply) system) Nothing is • Indoor operation switch is OFF. • Same at left. •...
  • Page 70: System Control

    2-15. System Control System control refers to the link wiring connection for control of simultaneous-operation multi systems, group control, and main-sub remote controller control. 2-15-1. Basic wiring diagram 1 Single type Be careful to avoid miswiring when connecting the wires. (Miswiring will damage the units.) (for 3-phase outdoor unit) Example: Using a wireless remote controller with a system Ground...
  • Page 71 2-15-2. Setting the outdoor unit system address For basic wiring diagram (Set the system address: 1) 8 – 10 HP Outdoor unit control PCB OC (CN500, BLU) EMG (CN502, BRN) 63PH (CN027, WHT) 8 – 10 HP SILENT (CN037, WHT) FUSE (0.5A, F500) System address rotary switch PUMP DOWN (CN048)
  • Page 72 2-15-4. Indoor unit remote controller main-sub setting If a wired remote controller is used, set the wired remote controller to “Sub”. If 2 wireless remote controllers are used, set the wireless PCB (DIP switch) on the second remote controller to “Sub”. 2-15-5.
  • Page 73: E1 Type (For Link Wiring)

    E1 Type (for Link Wiring) 2-16. Caution This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit. This test run explanation describes primarily the procedure when using the wired remote controller. If link wiring is used, set the outdoor unit system address to allow the combination of indoor and outdoor units to be identified.
  • Page 74: Test Run Procedure

    2-17. Test Run Procedure Recheck the items to check before the test run. (See 2-18) Check the combination (wiring) of indoor and outdoor units. (See 2-21-1) Is system “single-type”? Is outdoor unit multiple? (See 2-21-2) How to Set the Outdoor Unit System Address Set the outdoor unit system address.
  • Page 75: Items To Check Before The Test Run

    2-18. Items to Check Before the Test Run Turn the remote power switch ON at least 12 hours in advance in order to energize the crank case heater. Fully open the closed valves on the liquid-tube and gas-tube sides. 2-19. Test Run Using the Remote Controller (1) Press and hold the remote controller button for 4 seconds or longer.
  • Page 76: Automatic Address Setting

    2-21. Automatic Address Setting 2-21-1. Basic wiring diagram Link wiring A terminal plug (black) is attached to each of the outdoor unit control PCBs. NOTE At only one outdoor unit, leave the terminal plug short-circuit socket on the “Yes” side. At all the other outdoor units, change the socket (from “Yes”...
  • Page 77 Case 2 If the power cannot be turned ON separately for the indoor and outdoor units in the system: The compressors must be run in order to automatically set the indoor unit addresses. Therefore perform this step after completing the refrigerant tubing work. (1) Turn ON the power to the indoor and outdoor units in all refrigerant systems.
  • Page 78 Case 4 If the power cannot be turned ON separately for the indoor and outdoor units in each system: (The compressors must be run in order to automatically set the indoor unit addresses. Therefore perform this step after completing the refrigerant tubing work.) All-systems automatic address setting: Display item code “AA”.
  • Page 79: Automatic Address Setting

    2-21-3. Checking indoor unit addresses Use the remote controller to check the addresses of the indoor units. Press and hold the button and button for 4 seconds or longer (simple settings mode, “ALL” appears on the remote controller). Then press the button and select the indoor address.
  • Page 80 2-22-2. Setting outdoor unit system addresses For the basic wiring diagram (Set the system addresses: 1, 2, 3...) Outdoor unit control PCB 8 – 10 HP 8 – 10 HP OC (CN500, BLU) EMG (CN502, BRN) 63PH (CN027, WHT) SILENT (CN037, WHT) System address rotary switch FUSE (0.5A, F500) (Set to “0”...
  • Page 81: Caution For Pump Down

    2-22-4. Indicating (marking) the indoor and outdoor unit combination number Indicate (mark) the number after automatic address setting is completed. (1) So that the combination of each indoor unit can be easily checked when multiple units are installed, ensure that the indoor and outdoor unit numbers correspond to the system address number on the outdoor unit control PCB, and use a magic marker or similar means which cannot be easily removed to indicate the numbers in an easily visible location on the indoor units (near the indoor unit nameplates).
  • Page 82 – MEMO – 2-24...
  • Page 83: Section 3. Electrical Data

    3. ELECTRICAL DATA 3-1. Outdoor Units (Electric Wiring Diagram, Schematic Diagram) ........ 3-2 3-2. Indoor Units (Electric Wiring Diagram, Schematic Diagram) ........3-4 High-Static Pressure Ducted Type...
  • Page 84 3-1. Outdoor Units Electric Wiring Diagram U-200PE1E8 / U-250PE1E8...
  • Page 85 3-1. Outdoor Units Schematic Diagram U-200PE1E8 / U-250PE1E8...
  • Page 86 3-2. Indoor Units High-Static Pressure Ducted Type S-200PE1E8 Electric Wiring Diagram...
  • Page 87 3-2. Indoor Units High-Static Pressure Ducted Type S-200PE1E8 Schematic Diagram...
  • Page 88 3-2. Indoor Units High-Static Pressure Ducted Type S-250PE1E8 Electric Wiring Diagram...
  • Page 89 3-2. Indoor Units High-Static Pressure Ducted Type S-250PE1E8 Schematic Diagram...
  • Page 90 – MEMO –...
  • Page 91: Section 4. Process And Functions

    4. PROCESS AND FUNCTIONS 4-1. Control Functions ....................... 4-2 4-2. Outdoor Unit Control PCB ..................4-8 4-3. Outdoor Unit Filter PCB FIL-C906VH8 ..............4-9 4-4. Outdoor Unit HIC Board HIC-C906VH8 ..............4-10 4-5. Outdoor Unit Control PCB (CR-C906VH8P) ............. 4-11 4-6.
  • Page 92: Control Functions

    4-1. Control Functions 1. Indoor Air Temprature Control The thermostat is switched on and off in accordance with T shown below. T= (Indoor air temperature) - (Temperature set with the remote controller) In the body thermostat mode Indoor air temperature = (Body sensor) - (Shift temperature *) (setting at factory shipment) In the remote controller thermostat mode Indoor air temperature = (Remote controller sensor) * Shift Temperature...
  • Page 93 2) Maximum and Minimum Frequency Control The compressor's inverter frequency is controlled in accordance with the model and operation mode. The maximum and minimum frequencies for each model are shown in the chart below. * There are cases in which frequency is limited with other control functions depending on operational conditions, so operations are not always carried out in accordance with the maximum frequencies listed below.
  • Page 94 5) Heating High-Load Prevention Control The following control is performed in the heating mode in accordance with the indoor heat exchanger temperature max (E1, E2). (See the chart below.) (1) The operational frequency of the compressor is decreased when the temperature enters the "M" zone. The operation frequency is modifi...
  • Page 95 7) Discharge Temperature Control The following control is performed to prevent the discharge temperature from rising abnormally in order to protect the inverter compressor. In accordance with the temperature of the discharge sensor TD, such controls are performed as to limiting the increase of inverter frequency, decreasing it or halting operation of the compressor.
  • Page 96 Heating Mask Time This refers to the shortest time that heating operations must be performed without defrosting operations being executed. The mask time for this model is 25 minutes. Defrosting operations will not be commenced until the defrosting mask time has elapsed, even if frost adherence has been detected.
  • Page 97 12) Demand Control There are two styles of demand operations available as methods of restraining power consumption. (1) Demand via External Input Demand input from an external source is carried out from the outdoor unit EXCT (CN030) PCB or the outdoor unit's serial/parallel I/O (optional).
  • Page 98: Outdoor Unit Control Pcb

    4-2. Outdoor Unit Control PCB Layout Diagram (CR-C906VH8P) Fuse (F101) RC_P (CN039) EXCT (CN030) SILENT (CN037) PUMP DOWN (CN048) A.ADD (CN047) Sensor at upper side of heat exchanger (C2) Sensor at lower side of heat exchanger (C1) Suction temp. (TS) Outdoor air temp.
  • Page 99: Outdoor Unit Filter Pcb Fil-C906Vh8

    4-3. Outdoor Unit Filter PCB FIL-C906VH8...
  • Page 100: Outdoor Unit Hic Board Hic-C906Vh8

    4-4. Outdoor Unit HIC Board HIC-C906VH8 4-10...
  • Page 101: Outdoor Unit Control Pcb (Cr-C906Vh8P)

    4-5. Outdoor Unit Control PCB (CR-C906VH8P) Explanation of Functions 2P (white): Automatic address setting switch Auto Address • If the system address switch (S002: set to 0 at time of shipment) setting is other than “0”(central (CN047) control), press this switch once to automatically set the addresses at all indoor units which are in the same system, and are connected to that outdoor unit.
  • Page 102 Quiet mode plug 2P plug (white): Enables operation in quiet mode. (CN037) • The outdoor unit fan and compressor frequencies are subject to limits during operation. • Low-noise operation is enabled when the relay is turned ON. (Non-voltage contact "a" ) •...
  • Page 103: Indoor Unit Control Pcb Switches And Functions

    4-6. Indoor Unit Control PCB Switches and Functions [Indoor unit control PCB] T10 (CN061): 6P plug (YEL) / Used for remote control operation. (Refer to the Remote Control Section.) Control items: (1) Start/stop input (2) Remote controller prohibit input (3) Start signal output (4) Alarm signal output EXCT (CN073): 2P plug (RED) / Can be used for demand control.
  • Page 104 For AC Fan Motor (CR-UXRP71B-P) EEPROM (IC010) EMG (CN044) POWER LED (D002) OC (CN040) JP001 EXCT (CN073) GRL (CN020) DISP (CN072) FAN DRIVE (CN032) CHK (CN071) T10 (CN061) 4-14...
  • Page 105: Section 5. Service Procedures

    5. SERVICE PROCEDURES 5-1. Meaning of Alarm Messages ..................5-2 5-2. Contents of LED Display on the Outdoor Unit Control PCB ........5-4 5-3. Symptoms and Parts to Inspect .................. 5-5 5-4. Details of Alarm Messages ..................5-8 5-5. Table of Thermistor Characteristics ................5-14 5-6.
  • Page 106: Meaning Of Alarm Messages

    5-1. Meaning of Alarm Messages 1. Contents of the alarm display on the remote controller Blinking: OFF: Wireless remote controller Lamp display Possible cause of malfunction Display Serial commu- Remote controller is Error in receiving serial communication signal(Signal from nication errors detecting error signal from main indoor unit in case of group control)Outdoor system Mis-setting...
  • Page 107 Blinking: OFF: Wireless remote controller Lamp display Possible cause of malfunction Display Ceiling panel connection failure Activation of Indoor protection Fan protective thermostat protective Float switch Alter. device DC fan error. Outdoor protection Discharge temperature trouble Open phase detected, AC power trouble No gas 4-way valve locked High cooling load...
  • Page 108: Contents Of Led Display On The Outdoor Unit Control Pcb

    5-2. Contents of LED Display on the Outdoor Unit Control PCB LED 1 LED 2 Remarks Power ON sequence 1. No communication from indoor units in system If it is not possible to advance to 3, 2. Communication received from 1 or more indoor units in system repeats 1 3.
  • Page 109: Symptoms And Parts To Inspect

    5-3. Symptoms and Parts to Inspect Remote Alarm Eliminating controller Judgement conditions Judgement and correction contents condition of alarm alarm display Recovery at restart 1. Check refrigerant cycle (gas Abnormal discharge Stops when temp. exceeds temperature error. leak). •Discharge temp. Alarm output on 4 pre-trips.
  • Page 110 Remote Eliminating controller Alarm contents Judgement conditions Judgement and correction condition of alarm alarm display Error in current Inverter halted after alarm Recovery at restart 1.Stops immediately even detection circuit. detected. when operations restarted. •AC current value Alarm output on 4 consecutive •Layer short on the is high, even while (pre-trips.)
  • Page 111 Remote Eliminating controller Alarm contents Judgement conditions Judgement and correction condition of alarm alarm display Settings failure Main unit in simultaneous Power reset recovery 1.Check inter-unit control operation multi control wiring. duplicated. 2.Check indoor unit (Outdoor unit detected) combination. Automatic address Insuffi...
  • Page 112: Details Of Alarm Messages

    5-4. Details of Alarm Messages Alarm Details (1-1) [Alarm “P29”] Start-up failure of the compressor (will not start up) Related parts • HIC PCB (Model: [U-200PE1E8, U-250PE1E8] HIC-C906VH8) • Outdoor unit control PCB (Model: [U-200PE1E8, U-250PE1E8] CR-C906VH8P) Start of defect diagnosis •...
  • Page 113 (2) [Alarm “P26”] Start-up failure of the compressor (will not start up) Related parts • HIC PCB (Model: [U-200PE1E8, U-250PE1E8] HIC-C906VH8) • Outdoor unit control PCB (Model: [U-200PE1E8, U-250PE1E8] CR-C906VH8P) Start of defect diagnosis • Filter PCB (Model: [U-200PE1E8, U-250PE1E8] FIL-C906VH8) Is the power voltage correct? Implement the same check processes for in the diagnosis fl...
  • Page 114 HIC-C906VH8 HIC + Resistance Between terminals Between terminals Resistance Resistance Tester terminal (+) Tester terminal (-) Tester terminal (+) Tester terminal (-) HIC + HIC – ~ 10 k HIC – HIC + 100 k HIC + ~ 5 k HIC –...
  • Page 115 (4) [Alarm "P22"] Outdoor unit fan motor drive circuit trouble Start of defect diagnosis Are the connectors CN003, CN005, CN041 and CN042 connected correctly to Correct the connections the outdoor unit control PCB? Does the fan rotate without resistance when spun manually after the connectors Fan motor trouble Replace CN003, CN005, CN041 and CN042 are...
  • Page 116 (5) [Alarms “F04,” “F06,” “F07,” “F08,” “F12”] Sensor trouble Start of defect diagnosis Are the connectors of the sensor 020 (C2), 021 (C1), 022 (TS), Correct the connections. 023 (TO) and 024 (TD) connected correctly to the outdoor unit control PCB ? Are the characteristics of resistance values of the Replace the sensors C2, C1, TS, TO...
  • Page 117 Sensor Temperature Display Function (Displayed regardless of operation and stop) The below check procedure can be used to display all remote controller, indoor unit, and outdoor unit sensor temperatures. <Check procedure> (1) Press and hold the button and button simultaneously for 4 seconds or longer.
  • Page 118: Table Of Thermistor Characteristics

    5-5. Table of Thermistor Characteristics (1) Outdoor Air Temp. (TO) Sensor, Intake Temp. (TS) Sensor, Heat Exchanger Temp. (C1) Sensor, Heat Exchanger Temp. (C2) Sensor -20 -15 -10 Temperature ( C) Temperature ( C) (2) Discharge Temp. (TD) Sensor 90 100 110 Temperature ( C) 5-14...
  • Page 119: How To Remove The Compressor

    5-6. How to Remove the Compressor Pay careful attention to prevent water or foreign objects from entering into the refrigerant tubing when removing or installing the compressor. Removing 1.After collecting the refrigerant in the system, replace nitrogen gas from the service port of the gas tubing valve. 2.Remove the sound absorbing material protecting the compressor.
  • Page 120: How To Remove The Electrical Component Box

    5-7. How to Remove the Electrical Component Box Removing 1.Remove the front panel and inspection panel from the outdoor unit. 2.Remove all local wires connected to the electrical component box. 3.Remove the wires (temperature sensor, coils of every sort of valve, pressure switch, fan motor and wires for connecting compressor) connected to the electrical component box in the unit.
  • Page 121: Symptom: Thermostat In Off Continues Or Cycles Off & On Too Frequently

    5-8. Symptom: Thermostat in OFF continues or cycles OFF & ON too frequently How to detect abnormality • Abnormality does not occur. Protective function can be checked when the outdoor maintenance remote controller is connected. Error Diagnosis Indoor control Adjust setting Setting temperature reaches the level set ON thermostat.
  • Page 122 – MEMO – 5-18...
  • Page 123: Section 6. Outdoor Unit Maintenance Remote Control

    6. OUTDOOR UNIT MAINTENANCE REMOTE CONTROL 6-1. Overview ........................6-2 6-2. Functions ........................6-2 6-3. Normal Display Operations and Functions ............. 6-3 6-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures ......................6-6 6-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History ......................
  • Page 124: Overview

    6-1. Overview What is the outdoor unit maintenance remote controller? Beginning with the DC-INV series of outdoor units, nonvolatile memory (EEPROM) is used in the outdoor unit PCB. In this way, the setting switches that were located on earlier PCBs have been converted to EEPROM data. This remote controller is an outdoor unit maintenance tool that is used to make and change the EEPROM set- tings.
  • Page 125: Normal Display Operations And Functions

    6-3. Normal Display Operations and Functions Normal display functions • Connect the special service checker wiring to the outdoor unit PCB. The connection is shown in the fi gure below. Interface for outdoor unit maintenance Outdoor unit remote controller (Optional, Servicing No.CV6233039848) control PCB RC (5P, red) Relay connector (2P, white)
  • Page 126 Display (functions) • Use the temperature setting buttons to change the item code. Item code Display contents Remarks 00 (1) Outdoor unit alarm contents (code): OFF when normal At initial status Blinking 8-alarm code display at pre-trip, LED (2) No. of indoor units connected in that refrigerant system Unit.
  • Page 127 *2: 7-segment, 4-digit display for remote controller timer display The connected unit Nos. are displayed as shown below, using the 7-segment 4-digit ( ) display and the colon. Display for unit Nos. 1 – 20 Not lit Not lit Not lit Not lit Meaning of display colon —...
  • Page 128: Monitoring Operations: Display Of Indoor Unit And Outdoor Unit Sensor Temperatures

    6-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures <Operating procedure> (1) Press and hold the button and button simultaneously for 4 seconds or longer to switch to temperature monitor mode. During temperature monitoring, “Service Monitor” is lit. (The display and operations are the same as when monitor mode is started from the unit remote controller.) (2) Press...
  • Page 129: Monitoring The Outdoor Unit Alarm History: Display Of Outdoor Unit Alarm History

    6-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History Displays outdoor unit alarms only. Does not display indoor unit alarms. Check the indoor unit alarm histories separately using the indoor unit remote controllers or other control device. <Operating procedure>...
  • Page 130 List of Item Codes (Some item codes cannot be set due to the type of models.) Item code Parameter Control system schedule Do not set Control system schedule Do not set Control system schedule Do not set Snowfall sensor operation 0 = No sensor, control performed 1 = No sensor, control not performed 2 = Sensor present, control performed...
  • Page 131 Setting mode 2 <Operating procedure> (1) Press and hold the button, button, and button simultaneously for 4 seconds or longer. (2) Use the temperature setting buttons to change the item code. The item codes and setting data are shown in the table below. (3) Use the timer time buttons to change the setting data.
  • Page 132 – MEMO – 6-10...
  • Page 133: Section 7. Remote Controller Functions Section

    7. REMOTE CONTROLLER FUNCTIONS SECTION 7-1. Simple Settings Function ..................7-2 7-2. List of Simple Setting Items ..................7-3 7-3. Detailed Settings Function ..................7-4 7-4. List of Detailed Setting Items ..................7-5 7-5. Simple Setting Items....................7-9 7-6. Detailed Setting Items ....................7-11 7-7.
  • Page 134: Simple Settings Function

    7-1. Simple Settings Function • This allows the filter lifetime, operating mode priority change, central control address, and other settings to be made for an individual or group- control indoor unit to which the remote controller used for simple settings is connected. When simple settings mode is engaged, operation stops at the individual or group-control indoor unit to which the remote controller for simple settings is...
  • Page 135: List Of Simple Setting Items

    7-2. List of Simple Setting Items Setting data Item code Item Description 0000 Not displayed 0001 150 hours Filter sign ON time 0002 2,500 hours (filter life time) 0003 5,000 hours 0004 10,000 hours 0005 Use the filter clogging sensor. 0000 Standard (setting at time of shipping) Degree of filter fouling Highly fouled...
  • Page 136: Detailed Settings Function

    7-3. Detailed Settings Function • This allows the system address, indoor unit address, and other settings to be made for the individual or group-control indoor unit to which the remote controller used for detailed settings is connected. When detailed settings mode is engaged, operation stops at the individual or group-control indoor unit where the remote controller used for detailed settings is connected.
  • Page 137: List Of Detailed Setting Items

    7-4. List of Detailed Setting Items Setting data Item Item code Description Description Description 0000 0001 0002 High Static Pressure 0003 0005 0006 Ducted (E1) Type 0007 0008 0010 0011 0001 0003 0005 0007 0009 0011 Indoor unit capacity 0012 0015 0017 0018...
  • Page 138 Setting data Item code Item Description 0000 5 minutes Forced thermostat ON (1B) 0001 4 minutes –10°C –010 –9°C –009 Cooling discharge –8°C –008 temperature shift 0010 10°C –10°C –010 –9°C –009 Heating discharge –8°C –008 temperature shift 0010 10°C 0001 ±...
  • Page 139 Setting data Item code Item Description 0000 No forced operation 0001 Forced operation for 1 minute Automatic drain pump operation Continuous operation 0060 None 0000 Ventilation fan operation 0001 Ventilation fan operated by remote controller. Wired remote controller 0000 Not used. (Body sensor is used.) Remote control sensor is used.
  • Page 140 Setting data Item code Item Description DC fan tap Purpose operating mode 0000 Standard Standard (setting at shipment) High ceiling use High ceiling setting 1 (with standard panel) Ultra long-life filter, oil guard panel, ammonia 0001 For low static- deodorizing filter, optical regenerative pressure filter Fan tap setting deodorizing filter...
  • Page 141: Simple Setting Items

    7-5. Simple Setting Items Item code Item Description Filter sign ON time setting Changes the indoor unit filter lifetime when a high-performance filter or (filter lifetime) other optional product is installed. Reduces the filter sign ON time to 1/2 of the standard time (setting at the Degree of filter fouling time of shipping) for cases when filter fouling is more severe than normal.
  • Page 142 When the operating mode at the priority remote controller is changed, the operating modes of other remote controllers change as shown below. Mode change at priority remote controller Operating modes at other remote controllers Current mode New mode Current mode New mode Cooling or dry Heating...
  • Page 143: Detailed Setting Items

    7-6. Detailed Setting Items Item code Item Description Unit type Set when the indoor unit EEPROM memory is replaced during servicing. Indoor unit capacity System (outdoor unit) These are not set at the time of shipping from the factory. address These must be set after installation if automatic address setting is not Indoor unit address performed.
  • Page 144 Item code Item Description 1F (Upper limit) Cooling 20 (Lower limit) This setting changes the temperature range (upper limit and lower 21 (Upper limit) Change to the Heating limit) which is set from the remote controller or central control device. 22 (Lower limit) remote control The set upper limit must be greater than or equal to the lower limit.
  • Page 145 (Continued from previous page) Item code Item Description Heat exchanger The heat exchanger temperature control point for prevention of cold temperature for cold air air discharge during heating operation can be changed. discharge The indoor unit PCB optional output for the fan can be switched Fan output switching according to the purpose of use.
  • Page 146: Remote Controller Servicing Functions

    7-7. Remote Controller Servicing Functions • The remote controller includes a number of servicing functions. Use these as needed for test runs and inspections. List of Servicing Functions Functions Description Button operation Reset operation Unit status Operation with forced Press and hold the button for 4 Test run thermostat ON...
  • Page 147 Sensor Temperature Display Function (displayed regardless of whether unit is operating or stopped) The procedure below displays the sensor temperatures from the remote controller, indoor unit, and outdoor unit on the remote controller. <Procedure> Press and hold the buttons simultaneously for 4 seconds or longer. The unit No.
  • Page 148 – MEMO – 7-16...
  • Page 149: Section 8. How To Install The Wireless Remote Controller Receiver

    8. HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER RECEIVER Warning 8-1. Warning about Installation of Receivers ..............8-2 8-2. Warning about Installing Remote Controls ..............Optional Controller (Remote Controller) ................. 8-3. Names and Functions ....................8-4. Installing Batteries ....................... 8-5. Setting the Current Time .................... 8-6.
  • Page 150: Warning

    Warning 8-1. Warning about Installation of Receivers The wireless remote uses a very weak infrared light for its signal, which can result in the signal not being received because of the following influences, so take care in where the unit is installed. ·...
  • Page 151: Optional Controller (Remote Controller)

    Optional Controller (Remote Controller) Wireless Remote Controller / CZ-RWSC2 One remote control can control a group of up to eight indoor units. 8-3. Names and Functions REMOTE CONTROLLER 1. Operation Display Displays the operation status. 15. Sensor button Use this when switching to detect the temperature at the remote control.
  • Page 152 RECEIVER CZ-RWSC2 1. Receiver Receives the signal sent from the remote control. 2. Emergency Display lamps operation When an error occurs, one of the button lamps flashes. When a display lamp is blinking, refer to " Before Requesting Service ". Operating lamp This lamp is lit when the unit is operating.
  • Page 153: Installing Batteries

    8-4. Installing Batteries 1. Remove the cover. 2. Insert two AAA alkaline batteries. Put the batteries in with the polarity [+/–] as shown in the figure. 3. Gently insert one end of an unfolded paper clip (or a similar object that can Reset hole fit) into the Reset hole and press the Reset button inside the hole and then Cover...
  • Page 154: Timer Operation

    Stop: Press When the unit is stopped with the remote control, even though the compressor of the outdoor unit stops, the fan on the outdoor unit may continue to run for a while. If the unit is not heating very effectively with a Low fan speed , switch the fan speed to High Medium.
  • Page 155: Adjusting The Wind Direction

    Changing a timer setting • Press for the or the , and then when the timer setting is displayed, press for the timer again. Canceling a timer setting • If you press [CANCEL], the timer setting is canceled. • If you wish to cancel the setting for either the or the timer, press or the desired timer...
  • Page 156: For Best Results

    8-11. For Best Results Don’t get the remote control too far away from the receiver. This may cause a malfunction. Be sure to keep the remote control in the same room as the receiver. Point the remote control at the receiver. When the signal is received correctly it will beep one time.
  • Page 157: Emergency Operation

    8-13. Emergency Operation Use [Emergency Operation] in the following situations when there is an urgent need. • When the remote control's batteries have failed. CZ-RWSC2 • When the remote control is broken. • When the remote control is lost. 1. Press [Emergency Operation] of the receiver If the indoor temperature is 24°C or greater when the unit starts running, it will act as a cooler.
  • Page 158: Before Requesting Service

    8-15. Before Requesting Service Before requesting service, please check the followings. Problem Cause Solution The unit doesn’t work The power to the indoor unit is not ON. Make sure the power to the indoor unit is ON. even when is pressed Is the Normal/Stop All switch in the Stop All Switch it to the Normal position and cancel on the remote control.
  • Page 159 3. Things to remember when wired and wireless remotes are installed at the same time Two remote controls can be used to control the unit if the wireless remote control kit is installed at the same time as the wired remote control. (Up to 2 remotes [a wireless remote kit and the wired remote control] can be installed.) When using 2 remotes, one or more units can be operated by the remotes.
  • Page 160 4. Accessories Accessories Quantity Accessories Quantity Receiver Users Manual (Enclosed 200 mm wiring) Truss self-tapping screws 4 X 16 Remote controller Machine screws Remote controller's holder Wood screws AAA alkaline batteries Cable tie 5. Installing the Receiver Unit When using a separately installed receiver as a built-in model, install it to the JIS switch box (field supply) shown in the diagram on the right, which has been built into the wall on site in advance.
  • Page 161 When using a receiver that has been installed separately into the ceiling, use the enclosed fittings for installing to a ceiling. (1) Remove the metal plate of the receiver by slipping a flathead screwdriver or the like into the cut-out on the bottom. (2) Cut out a hole in the ceiling to match the dimensions of the enclosed template.
  • Page 162 NOTE When wiring remote controls, be sure to double-check the terminal numbers of the indoor unit connecting them so there are no mistakes in the wiring. (Damage will occur if high voltage [e.g. supply voltage] is applied.) If the wiring to the operation panel is bundled together with other wiring, such as the incoming line from the power source, it can cause a malfunction, avoid doing so.
  • Page 163 9. The Self-Diagnosis Function Display and What is Detected Alarm Display in the table below indicates the content of alarms that are displayed when a wired remote control is connected. For information on how to deal with the alarms, refer to the Mounting Instructions for the indoor unit or to Test Run or servicing materials.
  • Page 164 11. Setting Up Remote Control Functions The functions of the wireless remote can be set on site. (These settings are saved in nonvolatile memory in the remote control, so even when its batteries are changed, the settings do not revert to the defaults.) NOTE The operation of the air conditioner can be impacted, depending on the settings made, so only service personnel should make the settings.
  • Page 165 201210...

This manual is also suitable for:

S-250pe1e8U-200pe1e8U-250pe1e8

Table of Contents