CHECKLIST AFTER INSTALLATION WORK
Work List
No.
Are the indoor units installed following the
Installation
1
content on page 1-12-2-2-1 "SELECTING
THE INSTALLATION SITE"?
In the case of multiple installation: Is there
2
a wrong tubing connection with another
system?
In the case of multiple installation: Is there
3
a wrong wiring connection with another
system?
Is the earth leakage circuit breaker
4
(all-pole switching function provided)
installed?
Is there any wrong installation of optional
5
parts or wrong wiring?
Tubing &
Wiring
6
Was the ground wire work performed?
Are there any wrong power supply wiring,
7
wrong connection wire, wrong signal wire
or loose screw?
Is the thickness of wire in accordance with
8
rule?
Is the power-supply voltage equal to the
9
nameplate of the unit?
Was the check of the airtight test, fl ared
10
tube fi tting and gas leakage on the
welded portion performed?
Has the adhesive been applied to the
11
drain connecting portion (resin portion) of
the indoor unit?
Drain
12 Is there water leakage?
Check
Indoor unit drain pipe has a downward
13
gradient (1/100 or more) by rule. Is the
drain water fl owing smoothly?
Was the heat insulation work at a suitable
Heat
location including the fl ared tube fi tting
14
Insulation
(refrigerant tube & drain pipe) performed
properly?
Was the short-circuit connector connected
Optional
15
or the fan tap changed when installing the
Parts
air-blocking material?
16 Did the abnormal sound occur?
Test Run
Did the cool and warm airfl ow discharge
17
from the indoor unit?
Content
Check  
1-12-2-2-28
Possibility of Failure & Checkpoint
There is a possibility of light injure or loss of
property.
The unit is inoperated or the refrigerant fl ows
into the inoperative unit and the leakage is
expected. Check if there is a wrong tubing or wiring
connection with another system.
Power failure or short circuit may cause electric
shock or fi re. Check installation work and ground
wire work.
If the gas leakage occurs, the unit quality not only
becomes inferior but affects environment. Repair it
as quickly as possible.
The resin portion cracks after a few months and it
may cause water drain.
Since there is a possibility of water drain, repair the
drain pipe if the drain failure or water drain occurs.
The quality of unit not only becomes inferior but
there is a possibility of the water drain. So, perform
the heat insulation work properly.
The discharge temperature decreases in cooling
mode according to the reduction of air volume
and there is a possibility of dew drops. Be sure to
change settings.
Check if there is a fan contact or distortion of the
indoor unit.
Check if the unit does not operate or there is a
wrong tubing or wiring connection with another
system.