Panasonic Elite Big PAC-i S-200PE3E5B Technical Data & Service Manual page 6

Dc inverter
Hide thumbs Also See for Elite Big PAC-i S-200PE3E5B:
Table of Contents

Advertisement

Check of Density Limit
U-200PZH2E8, U-250PZH2E8
The refrigerant (R32), which is used in the air conditioner, is a flammable refrigerant. So the requirements for installation space of
appliance are determined according to the refrigerant charge amount [m
The minimum indoor floor space compared with the amount of refrigerant is roughly as follows:
45.0
40.0
35.0
30.0
25.0
20.0
15.0
10.0
5.0
0.0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5
[m
] : The refrigerant charge amount (Total of refrigerant at shipment and refrigerant charge amount in the field).
c
[m
] : Maximum refrigerant charge amount
max
U-200PZH2E8
U-250PZH2E8
m
max
[m
] ≤ 1.22 : Can be installed
c
1.22 < [m
] ≤ [m
] : Installation possible with in the range of slanted line part
c
max
[m
] > [m
] : Can not be installed
c
max
[m
] : the refrigerant charge amount (kg)
c
1.22
• 7.80 indicates m
digit of the model U-200PZH2E8, U-250PZH2E8.
max
7.80 kg
] used in the appliance.
c
Can be installed
Can not be installed
v
7.80

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents