Panasonic Elite Big PAC-i S-200PE3E5B Technical Data & Service Manual page 210

Dc inverter
Hide thumbs Also See for Elite Big PAC-i S-200PE3E5B:
Table of Contents

Advertisement

E15 Automatic Address Alarm (The total capacity of indoor units is too low.)
1.
Error Detection Method
Connecting indoor unit
It is judged an error the total capacity of indoor units replied by communication is lower than that of outdoor unit.
The total capacity of indoor units is lower than that of outdoor unit.
Some indoor unit(s) are connected but power is not turned on.
The CHK pin (CN062/CN071) and/or TEST pin (CN064) of the indoor unit is shorted when its power is turned on.
High voltage was applied (over AC200V) in the indoor/outdoor operations line circuit.
2.
Error Diagnosis
1 Power
1-1
Source
2
Indoor/
2-1
outdoor
control line
2-2
3 No. of
3-1
Indoor
Units
3-2
4 Indoor
4-1
unit
control
PC board
4-2
4-3
5
4-4
4-5
4-6
5 Outdoor
unit control
5-1
PC board
For information on the procedures for replacing the nonvolatile memory (EEPROM) of the indoor unit, refer to the manual
that is packaged with the indoor unit service board.
For information on the remote control's detailed settings, refer to the Reference Materials.
Indoor Unit Control PCB (ACXA73-3081*)
: S-200PE3E5B, S-250PE3E5B
POWER LED (D002)
EEPROM (IC010)
DISP (CN063)
JP001
CHK (CN062)
FAN DRIVE (CN032)
Is the indoor unit powered off?
Is the indoor/outdoor control line opened or shorted?
Was a high voltage (over AC200V) applied in the indoor/outdoor
operations line circuit?
Was the number of indoor units changed after auto address setting
finished?
Conduct checks prior to auto address setting.
Are the CHK pin and TEST pin on the indoor unit control board
short-circuited?
Is the wireless remote controller connected to on the indoor unit's
control PC board?
Disconnect the connector mentioned above on the control PC board
of the indoor unit control PC board and see whether the E15 goes off
after several minutes. (When doing so, if two remote controllers are
being used and the wireless remote controller is the main remote
controller, set the other remote controller as the main.)
Replace wireless remote control parts including wiring.
Is the LED blinking on the indoor unit's control PC board?
The nonvolatile memory (EEPROM) on the indoor unit's control board is either not installed,
improperly installed or the nonvolatile memory is faulty. Correct this or after replacing the
nonvolatile memory, write model data to it in the remote control detailed settings mode.
Check all items under the section "Check Prior to Auto Address Setting".
EXCT (CN073)
EMG (CN044)
OC (CN040)
T10 (CN061 )
Indoor Unit Control PCB (ACXA73-2553*)
: S-50PU2E5B, S-60PU2E5B, S-71PU2E5B, S-100PU2E5B,
S-125PU2E5B
FAN DRIVE (CN032)
DISP
CHK (CN062)
EEPROM (IC010)
OPTION (CN060)
EXCT (CN073)
T10 (CN061)
POWER LED (D002)
5-10
Yes
Power on
No
2-1
Yes
Correct the wiring
No
2-2
Yes
3-2
No
3-1
Yes
3-2
No
4-1
Yes
Remove the short
No
4-2
Yes
4-3
No
4-5
Yes
4-4
No
4-5
Yes
4-6
No
5-1
RC
JP001

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents