Panasonic Elite Big PAC-i S-200PE3E5B Technical Data & Service Manual page 215

Dc inverter
Hide thumbs Also See for Elite Big PAC-i S-200PE3E5B:
Table of Contents

Advertisement

H03 Primary Current CT Sensor (current sensor) Failure
1.
Error Detection Method
It is judged an error based on the criteria listed below.
If 18A or greater is detected when the compressor is stopped (alarm triggered even if the connector is unplugged).
If no current is detected even though a compressor is running.
2.
Error Diagnosis
1 Check the
Turn the power on again and run the outdoor unit.
1-1
control
Is alarm occurred after operation?
PC board
H05 Sensor Failure, Compressor Discharge Temperature Sensor (TD) Disconnected
1.
Error Detection Method
(In case of outdoor temperature over 5°C) For 10 minutes since started, variation of discharge temperature is always
detected within 2°C comparing with the temperature just before starting.
(In case of outdoor temperature less than 5°C) For 30 minutes since started, variation of discharge temperature is
always detected within 2°C comparing with the temperature just before starting.
1 Sensor
1-1
Is the sensor properly installed at the holder side?
Trouble
1-2
Replace the sensor with a new one.
5-15
Yes
Replace CR board.
No
See what happens.
Yes
1-2
No
Reinstall correctly.
5