1
Installing the Drain Pipe
CAUTION
Do not apply force to the drain port when connecting the
drain pipe. Install and fix it near the indoor unit as close
as possible.
Do not use adhesive when connecting the drain port pipe
and the drain hose.
(1) How to Install the Drain Pipe
1) First insert the supplied hose band into the drain port
pipe. Then make sure the head of the screw is facing
toward a technical engineer when placing the screw of
the hose band at an upward angle.
2) Insert the soft PVC socket of the supplied drain hose
to the drain port pipe. Do not use adhesive when
connecting the drain hose to the drain port pipe.
Insert it until the tip of the drain hose contacts the uneven
surface of the drain port pipe.
Drain port
(Drainage check section
on drain port, transparent)
* Drain port may possibly
be damaged and cause
the water leakage if
PVC adhesive is used.
Do not use adhesive here.
Fasten the hose band as shown the diagram
below. (Torque: 2.5 N·m - 3.4 N·m)
Uneven surface
* After checking the drainage, wrap the supplied packing and drain pipe insulator around the pipe.
Hose band (supplied)
Uneven
Soft PVC socket
surface
Indoor
unit
Indoor
unit
Packing
5 mm
(supplied)
3) Move the hose band so that the center position of the
hose band can be placed approx. 30 mm away from the
external plate of the indoor unit. See diagram below.
4) Screw the drain hose tightly facing the screw of the hose
band upward. (Torque: 2.5 N·m - 3.4 N·m) (If the screw
is tightened beneath the drain hose, the troubles will be
generated.)
5) Apply approx. 2 g of adhesive on both sides of the drain
hose without connection of the hard PVC socket and the
hard PVC pipe joint (VP25) in the local supply.
6) Connect the drain hose and the hard PVC pipe joint so
that the adhesive area of both sides can be overlapped.
Wipe off the protrusion-adhesive with a soft cloth.
Hard PVC pipe joint
Hard PVC socket
(VP25 field supplied)
Drain hose
(supplied)
* Apply approx. 2 g of adhesive on both sides
of supplied the drain hose and the hard
PVC pipe joint (VP25) in the local supply.
Wipe off the protrusion-adhesive with a soft
cloth.
Adhere with PVC adhesive.
57 mm
20 mm or more
Note:
Be sure to tightly insert the hard PVC pipe joint
(including elbow) minimum 20 mm or more.
* However, do not use the hard PVC
pipe joint allowable more than 55 mm
Drain insulator
insertion.
(supplied)
1-12-2-2-5