Panasonic Elite Big PAC-i S-200PE3E5B Technical Data & Service Manual page 259

Dc inverter
Hide thumbs Also See for Elite Big PAC-i S-200PE3E5B:
Table of Contents

Advertisement

Item code
Item
Automatic drain pump
operation
Ventilation fan operation
Wired remote controller
sensor
"Operation change control in
progress" display
OFF reminder function for
when weekly timer is used
Heat exchanger temperature
for cold air discharge
(Heat exchanger control
point for control to prevent
cold air)
Fan output switching
Drain pump delayed stop
time
Flap operation mode
Flap swing mode
No.
0000
No forced operation
0001
Forced operation for 1 minute
Continuous operation
0060
None
0000
0001
Ventilation fan operated by remote controller.
0000
Not used. (Body sensor is used.)
Remote controller sensor is used.
0001
Normal (displayed)
0000
Not displayed
0001
0000
None
0001
Only stop time setting is enabled.
0013
Control temperature 13°C
0014
Control temperature 14°C
0025
Control temperature 25°C
0026
Control temperature 26°C
0000
Output linked with fan. (ON when indoor unit fan is operating.)
0001
Fan mode operation output
0000
No delayed stop
0001
1 min. delayed stop
0002
2 min. delayed stop
0058
58 min. delayed stop
0059
59 min. delayed stop
0060
60 min. delayed stop
0000
Standard setting
Draft reduction mode (Flap lower-limit position is shifted
0001
upwards.)
Smudging reduction mode (Flap swing upper-limit position is
0000
shifted downwards.)
0001
Normal mode
Draft reduction mode (Flap swing lower-limit position is shifted
0002
upwards.)
7-9
Setting data
Description
(Continued)
7