Fujitsu Airstage J-II Series Design & Technical Manual page 861

Small vrf system
Table of Contents

Advertisement

●Operation status
46.4°F (8°C)
42.8°F (6°C)
Outdoor temperature
(Factory setting)
-0.4°F (-18°C)
-4°F (-20°C)
Outdoor temperature zone *
EEV ON/OFF
Heater
DIP-SW2-3 ON
Fan
DIP-SW2-3 OFF
* The Outdoor temperature zone transition from one to another will stay in that zone for
minimum 30 min.
NOTES :
● In following operations, EEV will be ON in Heat pump prohibition zone.
- Other than Heating
- Test Run
● This control is enable when the setting code no. 35 of the outdoor unit (Presence of heater
selection control by outdoor temperature) is "Enable".
Heat pump
prohibition
zone
ON
OFF
12 V
0 V
ON
OFF
ON
OFF
- (08 - 41) -
Combination zone