Fujitsu Airstage J-II Series Design & Technical Manual page 792

Small vrf system
Table of Contents

Advertisement

„ WIRED R.C.
z Step1: RB unit function setting (Case of VR-II series)
Set SET2 of DIP switch to "Priority given to administrative indoor unit" with function setting of
RB unit. (SET2-1:OFF, SET2-2:ON)
→Refer to 2-9. RB UNIT
z Step1: Outdoor unit function setting (Case of V-II)
Set to "Priority given to administrative indoor unit" with function setting of outdoor unit.
→Refer to 2-1. OUTDOOR UNIT
z Step2: Wired remote controller setting
(1) After the indoor unit stops operation, press the "MODE" button of wired remote controller
for 5 seconds continuously.
The operating mode of the wired remote controller display lights on after 5 seconds as
follows.
(1)-a) The indication not
set as "Administrative
indoor unit"
● "MODE " button is locked by below reasons while the marking
In such case, "Administrative Indoor Unit" cannot be set or released.
Operation Lock Display
● "Priority on Administrative Indoor Unit" is not selected in the setting of priority mode of outdoor unit.
→Set "Administrative Indoor Unit" in the wired remote controller after selecting "Priority on
Administrative Indoor Unit" in setting of priority mode of outdoor unit.
● Another indoor unit was set to "Administrative Indoor Unit" already.
→Release the setting "Administrative Indoor Unit" of another indoor unit.
(2) Press the "MODE " button.
Display (1)-b) when setting, and display (1)-a) when releasing.
→ The display blinks when the "MODE " button is pressed, and the display of (1)-a) and (1)-b)
alters whenever the "MODE " button is pressed.
→ The contents set in the wired remote controller are transferred to the indoor unit
immediately after the display is selected. It may take 10 seconds depending on
communication conditions. While this period, the button operation will be suspended.
→ It returns to the normal display after 20 seconds automatically if the operation button is
not pressed.
→ When setting or releasing is completed, the indication on wired remote controller changes
to the normal indication from blinking.
(3) Complete the setting or releasing of "Administrative Indoor Unit".
Press the "MODE " button of the wired remote controller again for 5 seconds continuously.
→ The indication returns to normal display if the "MODE" button is pressed for 5 seconds
continuously.
(It returns to normal indication after 20 seconds even if the "MODE " button is not pressed.)
(1)-b) The indication
set as "Administrative
indoor unit"
NOTES
- (07 - 145) -
lights on.