2-6. EXAMPLE OF PIPING DESIGN
„ REFRIGERANT SYSTEM 1
Outdoor
unit
b
(62.0kBtu/h)(52.5kBtu/h) (45.0kBtu/h) (37.5kBtu/h)(30.0kBtu/h) (22.5kBtu/h) (15.0kBtu/h)
BP1
BP2
a1
1
(9.5kBtu/h)
Indoor
unit
z System configuration
1
Model name
ARUL09
Capacity (Btu/h)
9,500
z System configuration
Outdoor unit
Model name
AOU60
Capacity (Btu/h)
60,000
z Capacity ratio
(Total indoor unit capacity) / (Total outdoor unit capacity)
= (62,000) / (60,000) = 103.3% (Within 50% to 130%)
z Selection of branch kit
Branch
Model
point No.
BP1
UTP-AX090A
BP2
UTP-AX090A
BP3
UTP-AX090A
BP4
UTP-AX090A
BP5
UTP-AX090A
BP6
UTP-AX090A
BP7
UTP-AX090A
a
c
d
BP3
BP4
b1
c1
2
3
(7.5kBtu/h)
(7.5kBtu/h)
Indoor
Indoor
unit
unit
(Indoor units)
2
3
ARUL07
ARUL07
ARUL07
7,500
7,500
7,500
(Outdoor unit)
Total cooling capacity of indoor units
connected downwards to the pipe.
e
f
BP5
BP6
d1
e1
4
5
(7.5kBtu/h)
(7.5kBtu/h)
Indoor
Indoor
unit
unit
4
5
6
ARUL07
ARUL07
7,500
7,500
Model
UTP-AX090A
- (06 - 22) -
g
h
(7.5kBtu/h)
BP7
f1
g1
6
7
(7.5kBtu/h)
(7.5kBtu/h)
Indoor
Indoor
unit
unit
Total
7
8
Capacity
(Btu/h)
ARUL07
ARUL07
62,000
7,500
7,500
Q'ty
7
8
(7.5kBtu/h)
Indoor
unit