 FORCED THERMOSTAT OFF FUNCTION
Function setting
60-00, 02, 05, 06, 08 0, 2, 5, 6, 8
*Edge input only
Example of cooling mode
On
CNA03 or
CNA04
Off
On
EEV
Off
Room temp.
Set temp.
NOTE :
● When the signal is received from another unit on the refrigerant circuit, there may be a
delay in thermostat off function at the unit.
z Example 1
- In - line connection
- Function setting for Fan setting when cooling thermostat OFF
Number 49-00 (Follow the setting on the remote controller)
Forced thermostat off is one of the function to save energy. For example, case of outdoor
temperature is lower than Indoor temperature, Indoor unit of air conditioner worked as Fan
operation based upon receiving signal from external controller. (Cooling Only)
Cooling operation
(Thermostat on)
Indoor
Temperature
Mode
External input
CNA03 or CNA04
(EXT.IN2)
External controller
Thermistor
Damper
Thermistor
Outdoor
Temperature
82˚F
88˚F
(28˚C)
(31˚C)
Office
Fri 10:00AM
Mode
Set Temp.
Fan
Custom
Cool
80°F
Auto
Auto
Heat
74°F
Cool
84°F
Room Temp.
Away
76°F
Heat
68°F
Vacation
Status
Menu
- (08 - 18) -
Input signal *
Command
OFF → ON
EEV OFF
ON → OFF
Normal operation
Fan operation
(Thermostat off)
Indoor
Temperature
Thermistor
Thermistor
Outdoor
Temperature
82˚F
75˚F
(28˚C)
(24˚C)
Office
Mode
Set Temp.
Custom
Cool
80°F
Auto
Heat
74°F
Cool
84°F
Room Temp.
Away
76°F
Heat
68°F
Vacation
Status